Multi-zone Heat Pump Condensing Units

S2HA DIMENSIONS AND SPECIFICATIONS

NOTE: All EMI products are subject to ongoing development programs so design and

specifications may change without notice.

S2HA ELECTRICAL SPECIFICATIONS

MODEL

(1)

VOLTS/HZ/PHASE

FAN

COMPRESSOR 1 COMPRESSOR 2 TOTAL

AMPS

MIN. CIR.

AMPS

(2)

HACR

BRKR

RLA

HP

RLA

LRA

RLA

LRA

9900

208-230/60/1

1.8

0.33

3.4

23

3.4

23

8.6

9.5

15

2200

208-230/60/1

1.8

0.33

4.3

27

4.3

27

10.4

11.5

15

9200

208-230/60/1

1.8

0.33

3.4

23

4.3

27

9.5

10.6

15

(1) Circuit Designators: 9 = 9,000 Btuh • 2 = 12,000 Btuh (ex. - Model 9200 consists of one 9,000 Btuh compressor and one 12,000 Btuh compressor)

(2) Always refer to the rating plate for Minimum Circuit Ampacity on all multiple compressor units.

S2HA PIPING SPECIFICATIONS

SOUND DATA

SHIPPING

WEIGHT

Model#

Line Sizes

Liquid

Suction

dBA

Lbs.

9900

1/4”

1/2”

64

159

2200

1/4”

1/2”

65

197

9200

1/4”

1/2”

65

187

Easy access interconnects

on back of unit

44”

38”

15”

Electrical

connections

Front of unit

1/2” Diameter Lag Holes

4.63”

4.63”

28.74”

12.44”

3.00”