6

Multi-zone Heat Pump Condensing Units

ELECTRICAL WIRING INSTALLATION SECTION

3. Use only HACR type breakers or time

delay fuses. Select the wire size accord-

ing to the ampacity rating.

4. To access electrical connections and

wiring diagram:
a) Remove the screws on the side panel

adjacent to the back panel.

b) The screws adjacent to the front

panel should already be loose (don't

remove them).

1. All electrical wiring must be run according

to NEC and local codes.

2. Refer to the unit rating plate for voltage,

minimum circuit ampacity and over cur-

rent protection requirements.

c. Slide the side panel out to access the

high/low electrical connections and

wire diagram.

Note: Remove the plastic edge guards

from the holes and replace with a water-

tight

strain relief fitting

(High V) and a

split grommet fitting (Low V)

5. Power should be run to a weather proof

disconnect box usually within 3 feet of

the unit.

6. From the disconnect box, run the power

through the 7/8" hole on the side of the

unit and into the electrical box and an-

chor with the strain relief fitting.

7. Run wires to the high Volt pigtail in the con-

trol box and attach L1 and L2 connections.

Also run green wire to ground wire.

The EMI America Series condensing

unit must:

• Be connected to a properly grounded

electrical supply with the proper voltage

as stated on the rating plate.

• Have proper over current protection (i.e.

time- delay fuse/HACR-Breaker) as listed

on the Rating Plate.

Failure to follow these instructions can re-

sult in a fire, explosion, or electrical shock

causing property damage, personal injury,

or death.

DANGER

!

!

Do not use the EMI America Series

condensing unit with any electrical supply

voltage other than the one listed on the

rating plate.
Check the rating plate on the unit for the

correct voltage rating. Failure to use the

correct voltage may result in death, serious

bodily injury or property damage. If you have

any questions or doubts, consult the factory

before installing this unit.

DANGER

!

!

Rating

Plate