Installation and Configuration

13

6.2

External Battery Cabinet Installation

Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery

run time. External battery cabinets are designed to be placed on one side of the UPS or stacked

beneath the UPS.
The external battery cabinet frame and battery kits are shipped separately. This 4U cabinet arrives

without internal batteries to lighten the cabinet for easier installation. Once the cabinet has been

placed in its final floor or rack position, the internal batteries may be installed.

When the external battery cabinet is received, it should be inspected for freight damage. Report dam-

age to the carrier and your local dealer or Liebert representative.
To install an external battery cabinet:
1. For slide rail installations, first remove the top/side fin by sliding it forward and lifting it up.

Optional rack-mount handles are shipped with the external battery cabinet and may be installed

now. (Securing hardware and slide rails are sold separately. Please contact your local dealer or

Liebert representative for these additional options and any assistance needed.)

2. Fasten the slides into position with the screws according to the instructions included with the

slide rails.

3. Use the enclosed support bases for the tower option to

prevent the assembly from tipping over. One additional set

of support base extensions ships with each external battery

cabinet.

4. Install the two battery packs and secure with the two

brackets supplied.

5. Connect the two slotted battery cables.
6. Attach the battery cover plate and the two front bezels.
7. Connect the supplied external battery cabinet cables to

either set of connectors on the rear of the external battery

cabinet, then to the rear of the UPS.

8. The UPS is now equipped with additional backup battery

run time. For approximate battery run times, refer to Table

6 - Battery run times in this manual.

9. Do NOT turn on the battery cabinet circuit breaker at this

time. Please complete the remainder of the installation first.

!

CAUTION

The external battery cabinet(s) are heavy (see 14.0 - Specifications). External battery

cabinets can be used in rack-mount or tower configuration. Take proper precautions when

lifting them.

!

CAUTION

Verify that the battery cabinet circuit breaker is in the OFF position. Do no energize the

battery cabinet at this time. When installation is complete, you will be instructed to turn on

the circuit breaker.

NOTE
UPS automatically detects the number of standard

batteries that are connected. The configuration program

may be used to set up the UPS for operation with non-

standard external batteries. Instructions for using the

configuration program follow in 8.0 - Configuration

Program.

+