Emerson Liebert GXT2-10000RT208 User Manual

Page 47

Advertising
background image

Troubleshooting

41

Fault indicator and diagnostic

indicators B and C are

illuminated.

REPO is currently activated.

UPS has shut down due to the REPO (Remote Emergency

Power Off). The output cannot be started by any method.

Fault indicator and diagnostic

indicators B and D are

illuminated.

UPS output is OFF from a

previous REPO command.

REPO is no longer activated.

UPS is OFF due to previous REPO (REPO is no longer

activated). Once utility power is restored, press the OFF

button twice within four seconds (to clear the alarm), then

press the ON button to start UPS (Auto-restart is NOT

possible).

Fault indicator and diagnostic

indicators C and E are

illuminated.

UPS shutdown due to a

command from the

communications port(s).

Your UPS has received a signal or command from the

attached computer. If this was inadvertent, ensure the

communication cable used is correct for your system. For

assistance, contact your local dealer, Liebert

representative or the Liebert Worldwide Support Group.

Fault indicator and diagnostic

indicators D and E are

illuminated.

UPS charger fault.

UPS requires service. Contact your local dealer, Liebert

Representative or the Liebert Worldwide Support Group.

AC Input indicator is On &

diagnostic indicators A, C and

E are illuminated.

On Internal Bypass to notify

user to move manual

maintenance bypass switch

to Bypass position.

Move manual bypass switch to the Bypass position, then

follow the instructions for replacing the UPS power module

(see 12.2 - UPS Power Module Replacement).

AC Input indicator is On &

Battery indicator is flashing.

Battery source is not

available; continuous horn.

Check battery connections, completely power down and

restart UPS.
NOTE: If the battery circuit opens while the UPS is

running, it will be detected when the next battery test is

performed.

Bypass indicator is flashing.

Bypass voltage is present,

but is disabled for use

because the voltage or

frequency is outside

acceptable limits.

The AC input powers the PFC input and serves as the

bypass source. If the AC is present but the voltage or

frequency exceeds the acceptable range for safe

operation with a load, the bypass will be disabled and this

indicator will flash, indicating that the bypass is

unavailable.

Table 5

Troubleshooting guide (continued)

Problem

Cause

Solution

Advertising