Isolate before opening control cabinet, Fig.4, Fig.7 5. maintenance – Sealey SAC65010B User Manual

Page 3: Fig.5, Fig.6

Advertising
background image

fig.4

4.2. Operation

WARNING! Ensure that you have read, understood and

apply Section 1 Safety Instructions.

IMPORTANT! The use of extension leads not

recommended as the resulting voltage drop reduces

motor, and therefore pump performance, and could

cause damage to the compressor.

NOTE: Take care when selecting tools for use with the

compressor. Air tool manufacturers normally express the

volume of air required to operate a tool in cubic feet per

minute (cfm). This refers to free air delivered by the

compressor (‘air out’) which varies according to the pressure

setting.

DO NOT confuse this with the compressor

displacement which is the air taken in by the compressor

(‘air in’). ‘Air out’ is always less than ‘air in’ due to losses

within the compressor.

In order to keep the compressor in good working condition,

periodic maintenance is essential.

IMPORTANT! Failure to carry out maintenance tasks may

invalidate the warranty on your compressor.

WARNING! Before performing any maintenance operation,

switch off the compressor, disconnect from the electricity

supply and release all air from the tank (except for 5.3.a)

5.1. Operations to be carried out after the first 50 working hours:

a) Check that all bolts/nuts are tight, particularly those retaining

the crankcase and cylinder head.

b) Replace the lubricating oil - see para 5.5.a. shown in fig.4.

5.2. Operations to be carried out weekly:

a) Drain condensation by opening the valve located under the

tank (fig.7). Place a container under the valve and open the

valve by turning anti-clockwise.

WARNING! Take care if there is still pressure inside the cylinder

as water could flow out with coinsiderable force.

Recommended pressure 1 - 2bar max.

b) Check oil level and, if necessary, top up.

fig.7

5. MAINTENANCE

Original Language Version

© Jack Sealey Limited

SAC65010B Issue: 1 - 24/12/14

fig.5

ISOLATE BEFORE OPENING

CONTROL CABINET

STARTING THE COMPRESSOR Refer to fig.5

4.2.1. Connect the mains supply and pull the pressure switch up to its

'on' position, see fig.7.

4.2.2. Turn the master power switch 'A' on the control unit to the 'I'

position - power On (signified by the white indicator light

'E' coming on.)

4.2.3.

Turn switch 'B' to start the compressor, position 1 is

compressor unit 1 operating only, position 2 is compressor unit

2 operating only, position 3 is both compressor units operating

at the same time, at staggered starting times (timer in fig.6).

4.2.4. When starting the compressor for the first time, leave it running

with no air tools connected to the air outlet. Make sure that the

pressure in the tank rises and that the compressor stops

automatically when the maximum pressure value allowed;

written on the plate and shown on the gauge

(fig.7) is

achieved. The compressor will now operate automatically.

The pressure switch stops the motor when the maximum tank

pressure is reached and restarts it when the pressure falls

below the minimum.

4.2.5. To stop the compressor, first turn the main switch "A" (fig.5) to

the '0' position and then turn the switch "B" (fig.5) to the '0'

position. The compressed air inside the compressor heads will

exhaust via check valves (fig.10), making the restart easier and

preventing the motors from being damaged.

DO NOT, other

than in an emergency

, stop the compressor by switching off at

the mains, or by pulling the plug out, as the pressure relief will

not then operate and motor damage may result upon restart.

4.2.6. The motors of the compressor are supplied with a manual reset

thermal-overload, located on the terminal board cover, see fig.6.

When the breaker is tripped, use the key to open the door, wait

for a few minutes, and reset the overloads manually.

4.2.7. The safety device is automatic. When the thermal overload is

tripped, wait for a few minutes to cool. The pressure switch is

released to the 'O' Off position.

NOTE:

a) If the motor does not cut in and out, but runs continuously

when using an air appliance, the capacity of the compressor

may be too small for the equipment or tool.

b) The gauge (fig.7) indicates the pressure inside the main

tank,

not the pressure supplied to the air equipment.

Should the pressure in the main tank exceed the pre-set switch

maximum, the safety valve will activate.

WARNING! For this reason DO NOT tamper with, or adjust,

the switch or safety valve.

fig.6

On/Off switch sited on the tank (fig.2)

Advertising