Clearances – Empire Comfort Systems VFYR-24SO-1 User Manual

Page 8

Advertising
background image

Page 8

12409-2-0403

Non-Combustible

Requirements for

Material Distance

Safe Installation

12" or more

Non-combustible material.

Less than 12"

Non-combustible material must be extended
to at least 8" with the installation of the
optional fireplace hood. If you cannot extend
non-combustible material at least 8", you
must operate heater with flue damper open.

CLEARANCES

10" and less Mantel

HEATER IN FIREPLACE

OR FIREBOX

28"

12"

HEAT RESISTANT
MATERIAL
12" WITHOUT
HOOD

Minimum Dimensions For Solid Fuel Burning Fireplaces
UL127 Factory Built Fireplaces

(Figure 2)

Model

A

B

C

D

VFYM-16

18"

13"

24"

18"

VFYR-16

18"

13"

24"

18"

VFYM-18

17"

14"

28"

17"

VFYR-18

17"

14"

28"

17"

VFYM-24

23"

14"

30"

18"

VFYR-24

23"

14"

30"

18"

VFYM-30

26"

14"

34"

20"

VFYR-30

26"

14"

34"

20"

Figure 2

The dimensions shown and defined in the fireplace manufacturer’s
instructions are minimum clearances to maintain in installing this
heater. Left and right clearances are determined when facing the
front of the heater.

Follow these instructions to ensure safe installation.

Failure to follow instructions exactly can create a fire hazard.

Sidewall & Ceiling Clearances (Figure 3)

Figure 3

The sides of the fireplace opening must be 6" from any combus-
tible wall. The ceiling must be at least 36" (for the 16" log) and
41" (for 18", 24" and 30" logs) from the fireplace opening.

MANTEL CLEARANCES (Figure 4)
Minimum non-combustible material clearance.
If not using hood.
You must have non-combustible materials above the fireplace
opening. Non-combustible material must extend at least 12" above
fireplace opening. With sheet metal, you must have non-
combustible material behind it.
Heat resistant materials such as slate and marble must be at least
1/2" thick. Sheet metal should not be installed onto
combustible material.
Important:
If you can not meet these minimum clearances, you

must operate this heater with chimney flue damper
open, if possible. See instructions for vented
operations.

If above minimum clearances can not be obtained, you must
use a hood.

Figure 4

18", 24", 30" Log

41"

16" Log

36"