Technical characteristics, Rotary disconnect switches – Eaton Electrical Disconnect Switches User Manual

Page 18

Advertising
background image

For more information visit us at: www.eatonelectrical.ca

17

December 2004

Technical Characteristics

Table 16. IEC Non-Fusible/Fusible Disconnect Switches from 32 to 1250 A

Value on left = non-fusible/ value on right = fusible.

Cable vs busbar connection on fusible @ 630A.

Busbar vs cable connection on fusible @ 800A.

Description

Catalogue Number

C362UC30
C362UC30CT
C363UC30JT

C363UV30C
C363UV30J
C363UV30CT
C363UV30JT

C362UV60
C363UV60J
C363UV60JT

C362UV100
C363UV100J
C363UV100JT

C362UV200
C363UV200J
C363UV200JT

C362US400
C363UV400J
C363UV400JT

C362US600
C363UF600J

C362US800
C363UF800L

C362US1000 C362US1200

Rating Ampere

32

32

63

100

200

400

600/630

800

1000

1250

Rated Insulation
Voltage Ui (V)

800

750

750

750

750

1000

1000

1000

1000 1000

Rated Impulse
Voltage (Uimp)

8 kV

8 kV

8 kV

8 kV

8 kV

12 kV / 8 kV

12 kV

12 kV

12 kV

12 kV

Operation Current (A)
400 V AC – AC 22A
– AC 23A

32
32

32
32

63
63

100
100

200
200

400
400

630
630

800
800

1000
1000

1200
1000

690 V AC – AC 22A
– AC 23A

32
32

32
32

63
63

100
100

200
200

400
200/250

500/630

200/630

630/800

400/630

630
400

630
400

Motor Power (kW)

400 V AC – AC 23A

15

15

30

51

100

220

355

450

560

560

500 V AC – AC 23A

18.5

18.5

40

63

140

280

450

560

560

560

690 V AC – AC 23A

25

25

55

90

185

185/220

185/600

400/600

400

400

Maxi. peak let through
current (kA peak)

5.5

7.6

17.6

17.6/22

32

48/36

48/77

75/77

75

75

Connection

Minimum Cu
Cable Section (mm

2)

6

6

10

25

50

185

2 x 150

2 x 185

2 x 240

––––

Minimum Cu
Busbar Section (mm

2)

––––

––––

––––

–––

––––

––––

2 x 30 x 5

➁ 2 x 40 x 5

2 x 50 x 5

2 x 60 x 5

Rotary Disconnect Switches