Variable depth, Operating mechanisms with disconnect switches, Technical data and specifications – Eaton Electrical Disconnect Switches User Manual

Page 26

Advertising
background image

For more information visit us at: www.eatonelectrical.ca

25

December 2004

– Variable Depth

Technical Data and Specifications

Figure 15. Mounting Dimension Requirements

Table 18. Mounting Dimension Requirements
in Inches (mm)

Table 19. Line Lug Data

Dimension A = The required wire
bending spacing selected from Article
430-10 of the National Electrical Code.

Dimension B = Minimum or maximum
depth from inside of flange holding
operating handle to panel where
Disconnect Switch is mounted.
(Variable 7 to 16 inches.)

G

B

A

C

Datum

Datum

E

F

D

1.62

(41.1)

Min.

.62

(15.7)

Disconnect Switch Type

A

B

C

D

E

F

G

30A and 60A Non-fusible

30A and 60A Fusible

100A Non-fusible

See
Dimensions
Below

See
Dimensions
Below

1.56
(39.6)
1.56
(39.6)
1.75
(44.5)

.96

(24.4)

.96

(24.4)
1.10
(27.9)

4.00
(101.6)
4.00
(101.6)
5.50
(139.7)

3.50
(88.9)
3.50
(88.9)
3.38
(85.9)

7.12

(180.8)

9.75

(247.7)

7.12

(180.8)

100A Fusible

200A Non-fusible and Fusible

1.75
(44.5)
3.34
(84.8)

1.10
(27.9)
0.63
(16.0)

5.50
(139.7)
8.50
(215.9)

3.38
(85.9)
1.84
(46.7)

11.88
(301.8)
15.50
(393.7)

Disconnect Switch Size

Wire Size

30 Ampere
60 Ampere

100 Ampere
200 Ampere

#2 – 14 Cu/Al
#2 – 14 Cu/Al
1/0 – 14 Cu/Al
250 kcmil – #6 Cu/Al

Operating Mechanisms with Disconnect Switches

Advertising