4 maintenance schedule, Table 11 maintenance schedule, 5 record log – Emerson Series 600T User Manual

Page 87: Maintenance schedule, Record log, Table 11, Warning, Caution

Advertising
background image

Maintenance

75

7.4

Maintenance Schedule

The Liebert FS maintenance schedule consists of actions listed in Table 11.

7.5

Record Log

Set up a maintenance log to record scheduled checks and any abnormal conditions.
The log should have space for all metered parameter indications including phase readings, alarm

messages, mode of operation, air filter replacement date and observation notes.
A periodic walk-through inspection of the Liebert FS room is advised to check for visible and audible

indications of problems. Log the inspection, metered parameter indications and any discrepancies.

!

WARNING

Any maintenance on the system should be delayed by at least 10 minutes after system is shut

down to be certain all electronics have discharged. Use appropriate safety precautions to

ensure unit is disconnected and de-energized.

!

CAUTION

Unless specified otherwise, ONLY a Liebert-certified service technician should perform all

maintenance work. Failure to use a Liebert technician for maintenance actions, unless

specifically noted, may void your warranty.

Table 11

Maintenance schedule

Item/Action

Frequency

Service

Performer

Every

1 yr

Every

3 yrs

Every

6 yrs

Every

15 yrs

System Visual Inspection *

Check

or Test

Liebert/Owner

System Cleaning (if necessary)

Check

or Test

Liebert/Owner

System Testing

(and adjustments, if necessary)

Check

or Test

Liebert

PCM Capacitor Bank

Service or

Replace

Liebert

Flywheel Module

Check

or Test

Service or

Replace

Liebert

UPS Interconnection Kit (if option installed)

Check

or Test

Liebert

Air Filter (if option installed)

Check

or Test

Liebert/Owner

NOTE
The recommended System Visual Inspection every year should include a check and torque of

cabinet DC circuit breaker box lug connections and the DC ground; see the relevant section of

Appendix A.0 - UPS Interconnection Kits for torque requirements.

NOTE
Liebert may determine additional maintenance actions as necessary and issue service or

technical bulletins to address any additions.

NOTE
The optional inlet Air Filter in the cabinet will need to be replaced when it is sufficiently dirty

to significantly reduce the flow of air into the cabinet. Ambient conditions at the installation

site will determine the frequency of replacement if option is installed