Wcp dimensions and specifications – EMI High Wall Air Handler WCP User Manual

Page 2

Advertising
background image

made in rome, new York, usa

WCP Chilled Water air Handler

WCP Dimensions and Specifications

notE:

Due to EMI’s ongoing development programs, design and specifications may change without notice.

Enviromaster International LLC

5780 Success Drive, Rome, NY 13440

www.enviromaster.com

WCP PHYsICaL dImEnsIons

model

Width “a”

Height “B”

depth “C”

Width “d”

Width “E”

Width “F”

Width “G”

Width “H”

Width “I”

shipping

Wt.

09/12

36½”

14½”

10¾”

32”

9”

24½”

8”

18”

16”

85

15/18

47½”

14½”

10¾”

32”

10”

34½”

8”

18”

27”

115

24/30

57½”

14½”

10¾”

42”

10”

44½”

8”

27”

28”

115

36

57½”

17”

11¼”

42”

10”

44½”

10½”

25”

28½”

115

WCP ELECtrICaL sPECIFICatIons

model #

Volts/HZ/

Phase

Fan

total

amps

min.

Volt

min.

ampacity

(1)

max

Fuse (1)

FLa

HP

09A, 12A

115/60/1

0.64

0.03

0.64

104

0.8

15

09D, 12D

208/230/60/1

0.34

0.02

0.34

197

0.43

15

15A, 18A

115/60/1

1.2

0.083

1.2

104

1.5

15

15D, 18D

208/230/60/1

0.56

0.07

0.56

197

0.7

15

24A, 30A

115/60/1

1.2

0.083

1.2

104

1.5

15

24D, 30D

208/230/60/1

0.56

0.07

0.56

197

0.7

15

(1) If electric heaters are installed, use Min Amp and Max Fuse from Heater Options Chart.

dIsCHarGE aIr sPEEd and FLoW

(230V High speed Fan)

model

CFm

Coil

FPm

throw/Ft.

9/12

310

Dry

960

16

15/18

600

Dry

1412

26

24/30

750

Dry

1400

25

36

750

Dry

1400

25

WCP oBsErVEd

sound VaLuEs

(230V High speed Fan)

model

dba

9/12

48

15/18

51

24/30

54

36

54

WCP ELECtrIC HEat oPtIons

model

Voltage KW

Heater

amps

total

amps

min. Cir.

amps

max

Fuse

9/12

230

3

13.1

13.5

16.8

20

15/18

230

3

13.1

13.6

17

20

24/30

230

5

21.7

22.3

27.9

30

36

230

5

21.7

22.3

27.9

30

ConnECtIons

WCP

Chilled Line

size

drain size

1/2” I.D.

1/2” I.D.

5/8” I.D.

1/2” I.D.

5/8” I.D.

1/2” I.D.

3/4” I.D.

1/2” I.D.

Advertising