3.6. PHASE 5 – PREPARATION OF WALL FOR RECESSED INSTALLATION

The wall for recessed installation must be made during installation using fireproof material (such as fireproof

plasterboard). It must also be load-bearing and equipped with metal vertical uprights that rest on the floor.
Make an opening in the front of the wall for recessed installation measuring W=1240 mm and H=580 mm. The

distance of the hole from the floor depends on the height of the fire bed (see paragraph 3.2

Pase1 – Positioning

of Fireplace Stove Forma Puro115 and figure below). Reinforce the wall by placing two metal uprights flush with
the hole (one for each side) and one at a distance (centre of upright)

  of about 530 mm to the right of the hole

(looking at the wall for recessed installation from the centre of the room).
With the wall for recessed installation prepared as instructed, the De Chirico frame is fastened to the steel

elements.
Position the wall so that the axis of opening is aligned with the axis of the fireplace stove and so that it is

indented by 4 mm with respect to the external surface of the hood support (flush with the sides: see figures).

1240

580

MONTANTE
FILO FORO

MONTANTE

FILO FORO

530

=

=

PROFILO

COPRIBORDO

4

PARETE

SUPPORTO
CAPPA

MONTANTE

Insulate the wall for recessed insulation from the heat of the fireplace stove.

  The hood support is deep enough

to provide an air space between the unit and the wall where you can insert insulation, such as insulating panels

or fibre ceramic mat.