Sm87pb general arrangement – MEDC SM87BG User Manual

Page 4

Advertising
background image

iv. The O-ring should be fully seated in the groove and not fall out when fitting the bezel to the cover.
f. Place the new glass element into position on the cover and assemble the bezel over the top of the glass element.
g. Ensure the glass element stays central on the cover by holding down the glass with thumb through the hole in the centre
of the bezel.
h. Carefully use the glass element to depress the plunger until the glass is in full contact with the cover O-ring. Ensure there
is an even gap around the glass.
i. Without allowing the glass element to move, screw down the bezel until the bottom of the bezel is tightened against the
cover.

SM87PB GENERAL ARRANGEMENT

SM87PB units - operation

The unit is operated by lifting the flap on the front of the cover, then depressing the steel actuator underneath. Depending on
the unit type ordered, the actuator will either remain in its depressed position or return to its original position.

SM87PB units - resetting procedure

On the units with a latching mechanism, once operated, the actuator remains in its position. To reset the call point, lift the flap
on the front of the unit and insert the key (provided with the unit) into the slot in the front face of the actuator. The key should
be turned slightly to locate it in the actuator and pulled back to the initial position. The key can then be removed and the flap
lowered.

4.0 MAINTENANCE