MEDC DB16 User Manual

Page 5

Advertising
background image

6.0 CERTIFICATION/APPROVALS

IECEx units

IIB

Certified to IEC 60079-0, IEC 60079-1 and IEC 60079-7

Ex de unit (IEC certification No. IECEx BAS 12.0076X)

30W – Ex de IIB T3 Gb (-50°C to +40°C)

25W – Ex de IIB T3 Gb (-50°C to +65°C)

Ex de IIB T4 Gb (-50°C to +0°C) – alternative marking

The IECEx certificate and product label carry the IECEx equipment protection level marking

Gb

Where Gb signifies suitability for use in a Zone 1 surface industries area in the presence of gas.

IIC

Certified to IEC 60079-0, IEC 60079-1, IEC 60079-7 and IEC 60079-31

Ex de unit (IEC certification No. IECEx BAS 12.0077X)

30W – Ex de IIC T3 Gb (-50°C to +40°C)

Ex tb IIIC T110°C Db (-50°C to +40°C)

IP6X

25W – Ex de IIC T3 Gb (-50°C to +65°C)

Ex tb IIIC T110°C Db (-50°C to +65°C)

IP6X

The IECEx certificate and product label carry the IECEx equipment protection level markings

Gb and Db

Where Gb signifies suitability for use in a Zone 1 surface industries area in the presence of gas.

Db signifies suitability for use in a Zone 21 surface industries area in the presence of dust.

ATEX units

IIB

Certified to EN 60079-0, EN 60079-1 and EN 60079-7

Ex de unit (ATEX certification No. Baseefa04ATEX0166X)

30W – Ex de IIB T3 Gb (-50°C to +40°C)

25W – Ex de IIB T3 Gb (-50°C to +65°C)

Ex de IIB T4 Gb (-50°C to +0°C)

The ATEX certificate and product label carry the ATEX group and category marking:

II 2 G

Where:

Signifies compliance with ATEX

II Signifies suitability for use in surface industries

2 Signifies suitability for use in a zone 1 area

G Signifies suitability for use in the presence of gases

© Cooper MEDC 2013

07/13

Advertising