1.0 INTRODUCTION

The SL5 Status Lamps are constructed from glass reinforced polyester and polycarbonate and have been

designed specifically for use in areas of harsh environmental conditions.

The units are BASEEFA Ex e / Ex em certified and can be manufactured as an array with up to 5 off connected

lamp units. Each unit comes complete with a set of standard terminals (AKZ4 or AKZ2.5), with other options such

as external paint finishes and backplates available.


2.0 GENERAL SAFETY MESSAGES AND WARNINGS

All instructions and safety messages in this manual must be followed to allow safe installation of the device. The

device must only be installed and maintained by correctly trained site personnel/installers.

i.

To reduce the risk of ignition of hazardous atmospheres and shock, do not apply power to the device until

installation has been completed and the device is fully sealed and secured.

ii.

To reduce the risk of ignition of hazardous atmospheres and shock, keep device tightly closed when the

circuit is energised.

iii.

Before removing the cover for installation or maintenance, ensure that the power to the device is isolated.

iv.

Following installation, test the device to ensure correct operation.

v.

Following installation ensure a copy of this manual is made available to all operating personnel

vi.

When installing the device, requirements for selection, installation and operation should be referred to

e.g. IEE Wiring Regulations and the ‘National Electrical Code’ in North America. Additional national

and/or local requirements may also apply.

vii.

Cable termination should be in accordance with specification applying to the required application.

MEDC recommends that all cables and cores should be correctly identified. Please refer to the wiring

diagram in this manual (or separate diagram provided with the unit).

viii.

Ensure that only the correct listed or certified cable glands are used and that the assembly is shrouded

and correctly earthed.

ix.

Ensure that only the correct listed or certified stopping plugs are used to blank off unused gland entry

points and that the NEMA/IP rating of the unit is maintained.

x.

MEDC recommend the use of a sealing compound such as HYLOMAR PL32 on the threads of all glands

and stopping plugs in order to maintain the IP rating of the unit.

xi.

A suitable sealing washer must be fitted to all glands and stopping plugs fitted into the enclosure.

xii.

The internal earth terminal, where fitted, must be used for the equipment grounding and the external

terminal, if available, is for a supplementary bonding connection where local codes or authorities permit

or require such a connection.

xiii.

When installing the device, MEDC recommends the use of stainless steel fasteners. Ensure that all nuts,

bolts and fixings are secure.


3.0 INSTALLATION

The status lamps are mounted via 4 off Ø7mm mounting holes on the base of each unit or alternatively the units

may be mounted via 6 off Ø11.5mm mounting holes on an optional backplate, details of the fixing centres can be

found in section 4.


Units may be mounted to vertical, horizontal or angled surfaces.


The direct mount fixing holes have been designed to accept an M6 screw or bolt. The backplate fixing holes have

been designed to accept an M10 screw or bolt.

Access to Terminals

Unscrew the 4 off M5 screws (4.0mm A/F hexagon key) holding the cover assembly to the base. Keep the screws

in a safe, accessible location if non-captive. Remove cover assembly to gain access to the interior.


Once termination is complete, carefully push the cover assembly back onto the base, avoiding damage to the

mating surfaces. Replace the 4 off M5 fixing screws (maximum torque 4Nm) into the holes in the cover assembly

and tighten evenly, ensuring the O-ring is correctly seated in its groove during re-assembly