Input, Open collector output – Precision Digital PD6800 User Manual

Page 7

Advertising
background image

PD6800-0L1 Loop-Powered Process Meter

Instruction Manual

7

Input

ACCURACY

±0.03% of calibrated span ±1 count,
square root & programmable exponent accuracy range:
10-100% of calibrated span.

MULTI-POINT
LINEARIZATION

2 to 32 points

PROGRAMMABLE
EXPONENT

1.0001 to 2.9999

LOW FLOW CUT-
OFF

0-99999 (0 disables cutoff function)

TEMPERATURE
DRIFT

50 PPM/

C from -40 to 75C ambient

DECIMAL POINT

User selectable decimal point

MINIMUM SPAN

Input 1 & Input 2: 0.10 mA

CALIBRATION
RANGE

An Error message will appear if input 1 and input 2 signals
are too close together.
Input
Range

Minimum Span
Input 1 & Input 2

4-20 mA

0.10 mA

MAXIMUM
VOLTAGE DROP

Without Backlight or with
Externally-Powered (DC
Powered) Backlight

With Loop-Powered
Backlight

3.0 VDC @ 20 mA

6.0 VDC @ 20 mA

EQUIVALENT
RESISTANCE

150 Ω @ 20 mA

300 Ω @ 20 mA

EXTERNALLY
POWERED
BACKLIGHT

Voltage Range:

Maximum Power

9-36 VDC

9 VDC 12 VDC 24 VDC 36 VDC

0.2 W 0.25 W 0.5 W

0.75 W

INPUT
OVERLOAD

Over current protection to 2 A max.

Open Collector Output

RATING

Isolated open collector, 30 VDC @ 150 mA max.

ALARM OUTPUT

Assign to level or volume for high or low alarm trip point.

DEADBAND

0-100% FS, user selectable

ACKNOWLEDGE

Front panel ENTER button and external RESET terminals
resets output and screen indication.