Electromagnetic compatibility, Safety information – Precision Digital PD6800 User Manual

Page 9

Advertising
background image

PD6800-0L1 Loop-Powered Process Meter

Instruction Manual

9

Electromagnetic Compatibility

EMISSIONS

EN 61326:2006
Safety requirements for measurement, control, and la-
boratory use – Industrial
Group 1 Class A ISM emissions requirements

Radiated
Emissions

Class A

IMMUNITY

EN 61326:2006
Safety requirements for measurement, control, and la-
boratory use

ESD

±4 kV contact,
±8 kV air

RFI – Amplitude
Modulated

80-1000 MHz @ 10 V/m,
1.4-2.0 GHz @ 3 V/m,
2.0-2.7 GHz @ 1 V/m,
80% AM (1 kHz)

EFT

±2 kV DC mains, ±1 kV other

Telco Surge

±1 kV

CRFI

3 V, 0.15-80 MHz, 1 kHz 80% AM

SAFETY INFORMATION

WARNINGS

 Read complete instructions prior to installation and operation of the meter.
 Installation and service should be performed only by trained service

personnel. Service requiring replacement of internal components must be
performed at the factory.

 Disconnect from supply before opening enclosure. Keep cover tight while

circuits are alive. Conduit seals must be installed within 18" (450mm) of
the enclosure.

 Verify that the operating atmosphere of the meter is consistent with the

appropriate hazardous locations certifications.

 If the meter is installed in a high voltage environment and a fault or

installation error occurs, high voltage may be present on any lead

.

Advertising
This manual is related to the following products: