Riello UPS MultiCOM 401 User Manual

Page 13

Advertising
background image

13

EXAMPLES

In the following examples, when you see:
Index you have to refer to LIST OF PARAMETERS chapter;
xxxx don’t care about the word’s value.

Read word parameter (AKA=1):

Word 0

Word 1

Word 2

Word 3

Output:

0x1000 + Index

xxxx

xxxx

xxxx

Input:

xxxx

xxxx

xxxx

Value


Read Input mains voltage V1 (Index 12 [0x000C] UPS PARAMETER):

Output:

0x100C

xxxx

xxxx

xxxx


Read Output nominal power (Index 80 [0x0050] UPS PARAMETER):

Output:

0x1050

xxxx

xxxx

xxxx

Write word parameter (AKA=2):

Word 0

Word 1

Word 2

Word 3

Output:

0x2000 + Index

xxxx

xxxx

Value

Input:

xxxx

xxxx

xxxx

xxxx


Write code 20 [0x0014] in Command code register (Index 113 [0x0071] UPS PARAMETER), in
order to execute a battery test:

Output:

0x2071

xxxx

xxxx

0x0014


For further examples about this function, see PERMANENT PZD CONFIGURATION.

Read array.word parameter (AKA=6):

Word 0

Word 1

Word 2

Word 3

Output:

0x6000 + Index

YY00

YY is sub-index

of array

xxxx

xxxx

Input:

xxxx

xxxx

xxxx

Value

Write array.word parameter (AKA=7):

Word 0

Word 1

Word 2

Word 3

Output:

0x7000 + Index

YY00

YY is sub-index

of array

xxxx

Value

Input:

xxxx

xxxx

xxxx

xxxx


For further examples about this function, see USER DEFINED PZD SLOTS.