Riello UPS MultiCOM 401 User Manual

Page 18

Advertising
background image

18

Index

Data type

NOMINAL DATA

UNIT

73

÷77

78

Unsigned16 Output nominal voltage (star)

V

79

Unsigned16 Output nominal frequency

0.1*Hz

80

Unsigned16 Output nominal power

100*VA

81

÷83

84

Unsigned16 Battery nominal capacity (battery expansion included)

Ah

85

Unsigned16 Battery benches

(1 or 2)

86

Unsigned16 Battery type

Integer

87

÷112


Index

Data type

COMMANDS

UNIT

113

Unsigned16 Command code

(1)

Integer

114

Unsigned16 Shutdown delay time

Seconds

115

Unsigned16 Restore delay time

Minutes

116

Unsigned16

117

Unsigned16 Command result

(2)

Integer

118

÷120

Unsigned16

(1)

Refer to Command codes paragraph

(2)

Command result = Command code if command is handled from the UPS

Command result = Command code + 100 if command is NOT handled from the UPS
Command result = 0 if Command code is wrong

Index

Data type

SPECIAL FLAGS (SENTR UPS)

(3)

UNIT

121

Unsigned16 Byte 1 of “s = xx..” code / Byte 2 of “s = ..xx” code

Flag

122

Unsigned16 Byte 1 of “c = xx..” code / Byte 2 of “c = ..xx” code

Flag

123

Unsigned16 Byte 1 of “b = xx..” code / Byte 2 of “b = ..xx” code

Flag

124

Unsigned16 Byte 1 of “r = xx..-..” code / Byte 2 of “r = ..xx-..” code

Flag

125

Unsigned16 Byte 3 of “r = ....-xx” code / Byte 1 of “i = xx..-..” code

Flag

126

Unsigned16 Byte 2 of “i = ..xx-..” code / Byte 3 of “i = ....-xx” code

Flag

127

Unsigned16 Byte 1 of “a = xx..-....” code / Byte 2 of “a = ..xx-....” code

Flag

128

Unsigned16 Byte 3 of “a = ....-xx..” code / Byte 4 of “a = ....-..xx” code

Flag

(3)

In order to decode these registers, please refer to the UPS manual


CODE

COMMAND

1 (0x0001)

Command shutdown

2 (0x0002)

Command shutdown and restore

3 (0x0003)

Cancel command codes 1, 2, 12

12 (0x000C)

UPS on bypass

20 (0x0014)

Battery test

22 (0x0016)

Test panel