11

Dry

The dry setting is best suited to parts of the country where excessive

humidity is not generally a problem, where the summer months are usu-

ally dry. On a call for cooling the motor will ramp up to full capacity and

will stay there until the thermostat is satisfied. At the end of the cooling

cycle, the blower will ramp down to 50% of full capacity where it will stay

for 60 seconds. Then it will ramp down to zero.

Temperate

The temperate setting is best suited for most of the country, where nei-

ther excessive humidity nor extremely dry conditions are the norm. On

a call for cooling, the motor will ramp up to 63% of full capacity and will

stay there for 90 seconds, then will ramp up to full capacity. At the end

of the cooling cycle, the motor will ramp down to 63% of full capacity

and will stay there for 30 seconds, then will ramp down to zero.

SECTION IX: UNIT DATA

TABLE 6: Physical and Electrical Data - Cooling Only (60 Hz)

Models

MV12B

MV12D

MV16C

MV20D

Blower - Diameter x Width

10 x 7

10 x 10

10 x 10

10 x 10

Motor

HP

1/2

1/2

3/4

1

Nominal RPM

1200

1200

1200

1200

Voltage

230

Amps

Full Load (230)

4.3

4.3

5.0

7.0

Permanent Filter

1

Type

DISPOSABLE OR PERMANENT

Size

16 x 20 x1

24 x 20 x 1

20 x 20 x 1

24 x 20 x1

Filter Bulk Pack

1PF0601BK

1PF0604BK

1PF0602BK

1PF0604BK

Shipping / Operating Weight (lbs.)

75/71

88/82

88/82

94/88

1. Field Supplied.

TABLE 7: Electrical Data - Cooling Only (60 Hz)

Models

Total Motor Amps

Minimum Circuit Ampacity

Max. O.C.P.

Amps/Type

1

Minimum Wire

Size A.W.G.

60 Hertz

60 Hertz

208V

230V

208V

230V

12B

4.7

4.3

5.9

5.4

15

14

12D

4.7

4.3

5.9

5.4

15

14

16C

6.1

5.0

7.6

6.9

15

14

20D

7.8

7.0

9.7

8.8

15

14

1. OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.

TABLE 8: Conversion Table

kW & MBH Conversions - for Total Power Input Requirement

FOR

208V

OPERATION MULTIPLY

240V

TABULATED kW & MBH BY

.751

230V

240V

.918

220V

240V

.840