CONVENTIONAL LOW VOLTAGE CONTROL WIRING

(24 VAC)

The 24 volt power supply is provided by an internally wired low voltage

transformer which is standard on all models, However, if the unit is con-

nected to a 208 volt power supply, the low voltage transformer must be

rewired to the 208 volt tap. See the unit wiring label.
Field supplied low voltage wiring can exit the unit on the top right hand

corner or the right hand side panel. Refer to Figure 3.
Remove desired knockout and pierce foil faced insulation to allow wir-

ing to pass through. Use as small of a hole as possible to minimize air

leakage.
Install a 7/8” plastic bushing in the selected hole and keep low voltage

wiring as short as possible inside the control box.
To further minimize air leakage, seal the wiring entry point at the outside

of the unit.
The field wiring is to be connected at the screw terminals of the control

board. Refer to Figure 6 or 7.

The low voltage connections may be connected to the screw terminals

or the quick connect terminals. The screw terminals and the quick con-

nect terminals are physically connected on the control board.

FIGURE 6: Air Handler Control Board – Communications Connections

SPARE JUMPER

HEAT ENABLE JUMPER

HUMIDIFIER OUT PUT

EAC OUTPUT

THERMOSTAT CONNECTIONS

CONTINUOUS FAN JUMPER

BLOWER SPEED
JUMPERS

HUMIDSTAT
JUMPER

AC/HP JUMPER

All wiring must comply with local and national electrical code
requirements. Read and heed all unit caution labels.
It is possible to vary the amount of electric heat turned on during the
defrost cycle of a heat pump. Standard wiring will only bring on the
first stage of electric heat during defrost. See Heat Output and Limit
Connections and Table 4 for additional information on heat during
defrost cycle.

NOTICE

TABLE 2: Low Voltage Connections

Terminal Signal

Comment

R

24 VAC power (fused)

G

Continuous Fan operation

Y/Y2

Second or full stage

compressor operation

Y1

First stage compressor

operation

Not used with outdoor units

having one stage compressors.

W2

Second stage heat operation

W1

First stage heat operation

O

Reversing valve operation

24 VAC will be present at this

terminal when the MODE

jumper is in the AC position.

This is normal.

HUM

Humidity switch input

24 VAC will be present at this

terminal when the HUM STAT

jumper is in the NO position.

This is normal.

X/L

Connection point for

heat pump fault indicator

This terminal is a connection

point only and does not affect

air handler control operation.

COM

24 VAC common