Installation and User Guide (10/06)

0.4 amp max.(24V DC)

0.2 amp max.(-48V DC)

Power Consumption: 3 watts typical, 4 watts max.

3.7 PXES4P, DC-powered, -48VDC, 24VDC and 12VDC Installation

This section describes the proper connection of the -48VDC leads (or 24VDC,

12VDC leads) to the Direct DC power terminal

block on the PXES4P hardened media converter (as

shown in Figure above). The DC terminal block on

the PXES4P is located on the left side of the unit

and is equipped with three (3) screw-down lead

posts. The power terminals are identified as positive

(+) and negative (-), and they are floating inside the unit so that the user if desired may

ground either of the terminals. The chassis is “earth” or ground (GND).