3 specifications, electrical – KEPCO MAT Full Rack MAT 6V, 15V, 25V AND 36V MODELS User Manual

Page 11

Advertising
background image

MAT FULL RACK 022602

1-3

1.3

SPECIFICATIONS, ELECTRICAL

a) MAT Power Module Features And Specification

TABLE 1-1. MAT POWER MODULE FEATURES AND SPECIFICATIONS

PARAMETER

CONDITION

MAT POWER MODULE

1/3 RACK

2/3 RACK

FULL RACK

Input Voltage Range

USER

SELECTABLE

105-125 VAC
210-250 VAC

Input Current Max

115 VAC

7.0A

14.0A

21.0A

230 VAC

3.5A

7.0A

10.5A

Input Frequency

RANGE

47-63 Hz

Voltage/Current Adjust-

ment Range

RANGES

0 to 100% of rating, by preprogrammed setting,

within inherent resolution limits

Programming

Resolution

Voltage

0.024% Eo max (12 bits)

Current

0.024% Io max (12 bits)

Programming Accuracy

Voltage

0.024% Eo max

Current

0.1% Io max

Data Read Back

Accuracy via Digital Bus

Voltage

0.1% Eo max

Current

0.12% Io max

Source Effect

Voltage

0.001% Eo max

Current

0.005% Io max

Load Effect

Voltage

0.002% Eo max

Current

0.024% Io max or 4 mA (whichever is greater)

Time 8 Hour Drift

Voltage

0.01% Eo max

Current

0.02% Io max

Temperature

Coefficient/°C

Voltage

0.01% Eo max

Current

0.02% Io max

Ripple & Noise

Voltage

rms: 0.001% Eo max or 0.3 mV (whichever is greater)

p-p: 0.01% Eo max or 3 mV (whichever is greater)

Current

rms: 0.03% Io max

p-p: 0.3% Io max

Transient Recovery

Voltage

150

µ

sec to recover within 0.1% Eo max for 10% to 100%

step in rated load current

Temperature

Operating

0 to 50 °C

Storage

-20 to +70 °C

Cooling

Built-in fan, air exhaust to rear

Remote Sensing

Range

0.5 volts per lead (Provision for 4-terminal connection to load)

DC Output Isolation

Voltage

500 Vdc

Leakage Current

Output to chassis

5

µ

A rms or 50

µ

A p-p @ 115V a-c

Series/Parallel Operation

Consult Kepco application engineering

Output Display

3-1/2 digit LCD

Panel Meter

Switch selectable voltage/current

IndIcators

4 LEDs

Voltage and Current Mode,Output Enabled, Polarity
Reversed

Output Enable/Disable

Built in power and sensing relays controlled through IEEE
1118 bus

Polarity Reversal

Built in power and sensing relays controlled through IEEE
1118 bus

Advertising
This manual is related to the following products: