TABLE 11: DHG 15 TON SUPPLY AIR BLOWER PERFORMANCE

DHG180 - BOTTOM DUCT CONNECTIONS

1, 2

BLOWER

SPEED,

(RPM)

MOTOR

PULLEY

(TURNS

OPEN)

3

CFM

4500

5250

6000

6750

7200

ESP

4

BHP

KW

ESP

3

BHP

KW

ESP

3

BHP

KW

ESP

3

BHP

KW

ESP

3

BHP

KW

208 VOLT AND STANDARD DRIVE

850

6.0

5

0.9

2.4

2.1

0.6

2.9

2.6

0.3

3.4

3.0

-

-

-

-

-

-

870

5.5

1.0

2.5

2.2

0.7

3.0

2.7

0.4

3.5

3.1

-

-

-

-

-

-

915

4.5

1.1

2.6

2.4

0.8

3.1

2.8

0.5

3.6

3.2

0.2

4.1

3.7

-

-

-

965

3.5

1.2

2.7

2.5

0.9

3.2

2.9

0.6

3.7

3.3

0.4

4.4

3.9

0.2

5.0

4.5

980

3.0

1.3

2.9

2.6

1.0

3.4

3.0

0.7

3.8

3.4

0.5

4.5

4.0

0.3

5.1

4.6

1010

2.0

1.4

3.0

2.7

1.1

3.6

3.2

0.8

4.0

3.6

0.6

4.7

4.2

0.4

5.4

4.8

1040

1.0

1.6

3.2

2.9

1.3

3.8

3.4

1.0

4.4

3.9

0.8

5.0

4.5

0.6

5.6

5.0

FIGURE 13 : 208 VOLT AND HIGH SPEED DRIVE ACCESSORY

965

6.0

1.2

2.7

2.5

0.9

3.2

2.9

0.6

3.7

3.3

0.4

4.4

3.9

0.2

5.0

4.5

980

5.5

1.3

2.9

2.6

1.0

3.4

3.0

0.7

3.8

3.4

0.5

4.5

4.0

0.3

5.1

4.6

1025

4.5

1.4

3.1

2.8

1.2

3.6

3.2

0.9

4.1

3.7

0.7

4.8

4.3

0.4

5.5

4.9

1065

3.5

1.6

3.4

3.0

1.4

3.9

3.5

1.1

4.5

4.0

0.9

5.1

4.6

-

-

-

1125

2.0

1.9

3.6

3.2

1.7

4.4

3.9

1.4

5.0

4.5

1.2

5.8

5.2

-

-

-

1170

1.0

2.1

3.9

3.5

1.9

4.7

4.2

1.6

5.5

4.9

-

-

-

-

-

-

230/460 VOLT AND STANDARD DRIVE

870

6.0

4

1.0

2.5

2.2

0.7

3.0

2.7

0.4

3.5

3.1

-

-

-

-

-

-

915

5.0

1.1

2.6

2.4

0.8

3.1

2.8

0.5

3.6

3.2

0.2

4.1

3.7

-

-

-

965

4.0

1.2

2.7

2.5

0.9

3.2

2.9

0.6

3.7

3.3

0.4

4.4

3.9

0.2

5.0

4.5

980

3.5

1.3

2.9

2.6

1.0

3.4

3.0

0.7

3.8

3.4

0.5

4.5

4.0

0.3

5.1

4.6

1015

2.5

1.4

3.0

2.7

1.1

3.6

3.2

0.8

4.0

3.6

0.6

4.7

4.2

0.4

5.4

4.8

1050

1.5

1.5

3.1

2.8

1.2

3.7

3.3

0.9

4.2

3.8

0.7

4.9

4.4

0.5

5.7

5.1

1065

1.0

1.6

3.4

3.0

1.4

3.9

3.5

1.1

4.5

4.0

0.9

5.1

4.6

-

-

-

230/460 VOLT AND HIGH SPEED DRIVE ACCESSORY

980

6.0

1.3

2.9

2.6

1.0

3.4

3.0

0.7

3.8

3.4

0.5

4.5

4.0

0.3

5.1

4.6

1045

4.5

1.6

3.2

2.9

1.3

3.8

3.4

1.0

4.4

3.9

0.8

5.0

4.5

0.6

5.6

5.0

1065

4.0

1.7

3.4

3.0

1.4

3.9

3.5

1.1

4.5

4.0

0.9

5.1

4.6

-

-

-

1125

2.5

1.9

3.6

3.2

1.7

4.4

3.9

1.4

5.0

4.5

1.2

5.8

5.2

-

-

-

1170

1.5

2.1

3.9

3.5

1.8

4.7

4.2

1.6

5.5

4.9

-

-

-

-

-

-

1190

1.0

2.2

4.0

3.6

1.9

4.8

4.3

1.7

5.6

5.0

-

-

-

-

-

-

1

Blower performance includes a gas -fired heat exchanger, fixed outdoor air, 2” T/A filters and a dry evaporator coil.

2

Refer to the Static Resistance table.

3

DO NOT

close the pulley below one turn open.

4

ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been
deducted from the total static pressure of the blower.

5

The factory setting.