Instructions for the installer – DE DIETRICH DTG1195X User Manual

Page 19

Advertising
background image

7

room ventilation rules where appliance is installed

make reference to the legislation, in conformity

with the local regulations.

FOR THE U.K. ONLY

The room containing this hotplate should have an

air supply in accordance with BS 5440: Part 2:

1989.

-All rooms require an openable window, or

equivalent and some rooms will require a

permanent vent a well.

-For room volumes up to 5 m

3

an air vent of 100cm

2

is required.

-For room volumes between 5 m

3

and 10 m

3

an air

vent of 50 cm

2

is required.

-If the room is greater than 5 m

3

and has a door that

opens directly to the outside, then no air vent is

required.

If there are other fuel burning appliances in the

same room BS 5440: Part 2:1989 should be

consulted to determine the air vent requirements.

Gas connection

Make sure that the appliance is adjusted for

the gas type available (see the label under the

appliance). Follow the instructions indicated in

the chapter “gas

transformations

and adjustments”

for the possible

adaptation to

different gases.

The appliance

m u s t b e

connected to the gas system by means of stiff metal

pipes or flexible steel pipes having continuous

walls, in compliance with the regulations in force.

Some models are equipped with both cylindrical A

and conical B connectors for gas supply (fig. 7).

Please select the type which is correct for the

supply concerned.

The connection must not stress the gas ramp.

Once the installation is over, check the

connection seal with a soapy solution.

Electric connection

The connection to the electric grid must be carried

out by qualified personnel and in conformity with

the regulations in force.

The voltage of the electric system must correspond

to the value indicated in the label under the

appliance. Make sure that the electric system is

provided with an effective ground connction in

compliance with the regulations and provisions of

the law.

Grounding is compulsory.

If the appliance is not equipped with a plug, apply

a standardized plug to the power supply cable.

This device must be at a suitable opening distance

from the contacts in order to allow the entire

disconnection in case of overvoltage category III,

in accordance with installation rules.

GAS TRANSFORMATIONS AND ADJUSTMENTS

Replacing the nozzles

If the equipment is adjusted for a type of gas that is

different from the one available, it is necessary to

replace the burner nozzles.

The choice of the nozzles to replace must be

made according to the table of the “technical

characteristics” as enclosed.

Act as follows:

-

Remove the racks

and burners.

-

B y m e a n s o f

a straight spanner L,

unscrew the nozzle U

(fig.8) and substitute it with

the corresponding one.

-

Tighten the nozzle

strongly.

Adjusting the burners

The lowest flame point must always be properly

adjusted and the flame must remain on even if

there is an abrupt shift from the maximum to the

minimum position.

If this is not so, it is necessary to adjust the lowest

flame point as follows:

-start the burner up;

-turn the tap up to the minimum position (small

flame);

-remove the knob from the tap rod;

-introduce a flat-tip screwdriver C in the hole of

control panel of the tap (fig. 9) and turn the by-

pass screw V (fig.9/A) up to a proper adjustment

of the lowest flame point.

Fig.9

Fig.9/A

As regards G30 gas burners, the by-pass screw

must be tightened completely.

V

INSTRUCTIONS FOR THE INSTALLER

Fig.8

Fig.7

Advertising
This manual is related to the following products: