Specifications, Placement on subfloor, Under cooling support equipment – Emerson Liqui-tect 460 Kits User Manual

Page 2: Dimensions - top & front views, Prepackaged sizes for liebert units, Leak detection kit installation suggestions, Ordering information, Specifications placement on subfloor

Advertising
background image

2

Specifications

Placement on Subfloor

Under Cooling Support Equipment

Dimensions - Top & Front Views

Prepackaged Sizes for Liebert Units

Leak Detection Kit Installation Suggestions

Ordering Information

Liqui-tect 460 Module

Power requirements

24 VAC 120 mA, 50/60 Hz

3 VA (max.)

Enclosure dimensions

W x D x H

5.35" x 3.23" x 3.5"

(135.9mm x 82mm x 88.9mm)

Mounting hole dimensions See diagrams at right
Weight (assembled)

2.0 lb. (0.9 kg)

Sensing cable

compatibility

All Liebert LT500 sensing

cables

Maximum length of

sensing cable

100ft (30.5m)

Metal enclosure

NEMA 1, IP 30

Environmental Conditions
Operating temperature

50°F to 104°F (10°C to 40°C)

Operating humidity

10% to 95% relative humidity

(non-condensing)

Operating altitude

0 to 10,000 ft. (0 to 3,048m)

Output Relays
Contact rating

2 Form-C, 3 A rating at 24 VAC

Agency Listings
UL

UL916

C-UL

C22.2, No. 205-M1983

CE

Yes

FCC Compliance

47 CFR, Part 15

* Output connections to external alarm monitoring panels

such as the Liebert contact closure alarm panels

Leak detection

zone (directly

beneath unit)

Leak

detection

cable

To a Liebert

environmental

unit and an

optional*

monitoring

panel

To external

power

supply or

directly

from

unit

LT460

Scenarios

Upflow

Unit

Detection

around

entire unit

Upflow

Unit

Detection

on sides and

in front of unit

Downflow

Unit

Detection

around

entire unit

Downflow

Unit

Detection

on sides and

in front of unit

Distance:

Distance From Unit

In back

On sides

In front

2 ft

2 ft

2 ft

(No cable)

2 ft

2 ft

1 ft

1 ft

6 ft

(No cable)

1 ft

6 ft

Unit

(footprint-in.)

P

ART

N

UMBER

Challenger

(32.5 x 32.5)

LT460-Z30

LT460-Z20

LT460-Z30

LT460-Z25

Himod

(69 x 35)

LT460-Z35

LT460-Z20

LT460-Z35

LT460-Z25

Deluxe System/3

(50 x 35)

LT460-Z30

LT460-Z20

LT460-Z35

LT460-Z25

(74 x 35)

LT460-Z35

LT460-Z20

LT460-Z35

LT460-Z25

(99 x 35)

LT460-Z45

LT460-Z25

LT460-Z45

LT460-Z30

(122 x 35)

LT460-Z45

LT460-Z25

LT460-Z45

LT460-Z30

DS

(73 x 35)

LT460-Z35

LT460-Z20

LT460-Z45

LT460-Z30

(86 x 35)

LT460-Z35

LT460-Z20

LT460-Z45

LT460-Z30

(98 x 35)

LT460-Z45

LT460-Z25

LT460-Z45

LT460-Z30

(109 x 35)

LT460-Z45

LT460-Z25

LT460-Z45

LT460-Z30

(132 x 35)

LT460-Z45

LT460-Z25

LT460-Z45

LT460-Z30

4.75"

(121mm)

4.25"

(108mm)

3.25"

(83mm)

4.75"

(121mm)

2"

(51mm)

Shipping weight: 2 Ibs (0.9 kg)

Mounting holes: #8 screws

TOP VIEW

Leak

detection

cable

connector

Form-C

relay outputs

& power

wiring

connection

FRONT VIEW

Note:

indicates

placement

of LT460

module

2' clearance

in front

2' clearance

in front

6' clearance

in front

6' clearance

in front

Packaging

Quantity

Product Number

Description

Prepackaged

Kits

LT460-Z20

Zone Leak Detection Kit With Cable and Hold-Down Clips

20-Foot Cable

LT460-Z25

Zone Leak Detection Kit With Cable and Hold-Down Clips

25-Foot Cable

LT460-Z30

Zone Leak Detection Kit With Cable and Hold-Down Clips

30-Foot Cable

LT460-Z35

Zone Leak Detection Kit With Cable and Hold-Down Clips

35-Foot Cable

LT460-Z45

Zone Leak Detection Kit With Cable and Hold-Down Clips

45-Foot Cable

Available

Separately

LT460

Zone Leak Detection Module

LT500-15Y

Leak Detection Cable

15-Foot Cable

LT500-35Y

Leak Detection Cable

35-Foot Cable

LT500-50Y

Leak Detection Cable

50-Foot Cable

LT500-ET

End Terminator for LT500Y Cable

HDC

Hold-Down Clips

Advertising