Wiring to Auxiliary Alarm Panels

The LT460 has two Form-C dry contact alarm output contacts (TB2 & TB3). Each contact is rated for 24 VAC

at 3 amp.

Figure 3 LT460 to Liebert environmental units

Figure 4 LT460 to Liebert contact monitor panel

Liebert Deluxe Sys/3,
Challenger, Himod or
MM2 (8 Ton)

24

(24V)

51

LT460

TB2

TB2-2

(C)

TB2-1

(N.O.)

TB2-3

(N.C.)

Env. Unit

Liebert MM2 (1 to 5 Ton)

TB1-1

(24V)

TB1-2

LT460

TB2

TB2-2

(C)

TB2-1

(N.O.)

TB2-3

(N.C.)

Env. Unit

OR

TB2

TB2-2

(C)

TB2-1

(N.O.)

TB2-3

(N.C.)

Env. Unit

TB1-1

(24V)

TB1-3

Liebert MM2 (1 to 5 Ton)

LT460

TB2-3 (N.C.)

TB2

Liebert DS

LT460

TB2-2 (C)

TB2-1 (N.O.)

Environmental

unit

24 (24V)

50, 51, 55 or 56

TB2-3 (N.C.)

TB2

Liebert Deluxe System/3,

Challenger, Himod or

Mini-Mate2 (8 ton)

LT460

TB2

Liebert Mini-Mate2

(1 to 5 ton)

LT460

TB2-2 (C)

TB2-1 (N.O.)

TB2-3 (N.C.)

TB2-2 (C)

TB2-1 (N.O.)

Environmental

unit

Environmental

unit

24 (24V)

51, 55 or 56

TB1-1 (24V)

TB1-2 or TB1-3

TB2

TB2-2

(C)

TB2-1

(N.O.)

TB2-3

(N.C.)

LT460

Liebert Contact
Monitor Panel

Input

Contact

(N.O.)

Alarm Panel

TB2-3 (N.C.)

TB2-2 (C)

TB2-1 (N.O.)

TB2

LT460

Alarm panel

Liebert contact

monitor panel

Input

contact

(N.O.)