Normal data transfer – ProSoft Technology MVI69L-MBTCP User Manual

Page 69

Advertising
background image

MVI69L-MBTCP ♦ CompactLogix Platform

Backplane Data Exchange

Communication Module

User Manual

ProSoft Technology, Inc.

Page 69 of 152

January 6, 2014

All data transferred between the module and the processor over the backplane is
through the input and output images. Ladder logic is needed in the
CompactLogix processor to interface the input and output image data with data
defined in the Controller Tags. All data used by the module is stored in its internal
database. This database is defined as virtual MBTCP data tables with addresses
from 0 to 239 each.

4.2

Normal Data Transfer

Normal dat

a transfer includes the paging of the user data found in the module’s

internal database and the status data. These data are transferred through read
(input image) and write (output image) blocks. The following topics describe the
structure and function of each block.

4.2.1 Write Block: Request from the Processor to the Module

These blocks of data transfer information from the processor to the module. The
structure of the output image used to transfer this data is shown below:

Offset

Description

Length (words)

0

Write Block ID

1

1 to 240

Write Data

240

The Write Block ID is an index value used to determine the location in the
module’s database where the data will be placed.

4.2.2 Read Block: Response from the Module to the Processor

These blocks of data transfer information from the module to the processor. The
structure of the input image used to transfer this data is shown below:

Offset

Description

Length (words)

0

Read Block ID

1

1

Write Block ID

1

2 to 241

Read Data

240