Communication error codes – ProSoft Technology MVI69L-MBS User Manual

Page 101

Advertising
background image

MVI69L-MBS ♦ CompactLogix Platform

Diagnostics and Troubleshooting

Communication Module

User Manual

ProSoft Technology, Inc.

Page 101 of 154

January 6, 2014

6.5

Communication Error Codes

Standard Modbus Protocol Exception Code Errors

Code

Description

1

Illegal Function Code

2

Illegal Data Address

3

Illegal Data Value

4

Failure in Associated Device

5

Acknowledge

6

Busy, Rejected Message

Module Communication Error Codes

Code

Description

-1

CTS modem control line not set before transmit

-2

Timeout while transmitting message

-11

Timeout waiting for response after request

253

Incorrect slave address in response

254

Incorrect function code in response

255

Invalid CRC/LRC value in response

Command List Entry Errors

Code

Description

-41

Invalid enable code

-42

Internal address > maximum address

-43

Invalid node address (< 0 or > 255)

-44

Count parameter set to 0

-45

Invalid function code

-46

Invalid swap code

Note: If an error code is reported that is not listed above, check with the documentation of the end

device. Device-specific error codes can be produced by the end device.