MVI69L-MBS ♦ CompactLogix Platform

MVI69L-MBS Configuration

Communication Module

User Manual

ProSoft Technology, Inc.

Page 55 of 154

January 6, 2014

Additional Configuration Parameters as a Slave

Parameter

Value

Description

Minimum
Response Delay

0 to 65535
milliseconds

Sets the number of milliseconds to wait before responding to
a command received on the port from a remote Master. This
delay is sometimes required to accommodate slower Master
devices.

Internal Slave ID

1 to 247

Defines the Slave Node Address for the internal database. All
requests received by the port with this address are processed
by the module. Verify that each device has a unique address
on a network.

Bit Input Offset

0 to 479

Specifies the offset address into the internal Modbus
database for network requests for Modbus function 2
commands. For example, if the value is set to 150, an
address request of 0 returns the value at register 150 in the
database.

Word Input
Offset

240 to 479

Specifies the offset address into the internal Modbus
database for network requests for Modbus function 4
commands. For example, if the value is set to 350, an
address request of 0 returns the value at register 350 in the
database.

Output Offset

0 to 479

Specifies the offset address into the internal Modbus
database for network requests for Modbus function 1, 5 or 15
commands. For example, if the value is set to 100, an
address request of 0 corresponds to register 100 in the
database.

Holding Register
Offset

0 to 479

Specifies the offset address in the internal Modbus database
for network requests for Modbus function 3, 6, or 16
commands. For example, if a value of 250 is entered, a
request for address 0 corresponds to the register 250 in the
database.