7.2.10 Preset Multiple Registers (Function Code 16)

Query
This Function Code allows you to modify the contents of a Modbus 4x range in
the slave. This writes up to 125 registers at time. Since the controller is actively
scanning, it also can alter the content of any holding register at any time.

Note: Function codes 5, 6, 15, and 16 are the only messages that are recognized as valid for

broadcast.

The example below is a request to write 2 registers starting at register 40002 in
slave 11.

Node
Addrs

Func
Code

Data Start
Addrs

High

Data Start
Addrs

Low

Number
of

Points
High

Number
of

Points
Low

Byte
Count

Data
High

Data
Low

Data
High

Data
Low

Error
Check

Field (2
bytes)

0B

10

00

01

00

02

04

00

0A

01

02

CRC

Response
The normal response to a function 16 query is to echo the address, function
code, starting address and number of registers to be loaded.

Node
Address

Function
Code

Data Start
Address High

Data Start
Address Low

Number of
Points High

Number of
Points Low

Error Check
Field (2
bytes)

0B

10

00

01

00

02

CRC