MVI69E-MBS ♦ CompactLogix Platform

MVI69E-MBS Configuration

Communication Module

User Manual

ProSoft Technology, Inc.

Page 57 of 162

January 6, 2014

Additional Configuration Parameters as a Slave

The Type parameter must be “Slave” or “PassThru Slave” to configure these
parameters. See “Configuration Parameters Common to Master and Slave” on
page xx.

Parameter

Value

Description

Minimum
Response Delay

0 to 65535
milliseconds

Sets the number of milliseconds to wait before responding to
a command received on the port from a remote Master. This
delay is sometimes required to accommodate slower Master
devices.

Internal Slave ID

1 to 247

Defines the Slave Node Address for the internal database. All
requests received by the port with this address are processed
by the module. Verify that each device has a unique address
on a network.

Bit Input Offset

0 to 9998

Specifies the offset address into the internal Modbus
database for network requests for Modbus function 2
commands. For example, if the value is set to 150, an
address request of 0 returns the value at register 150 in the
database.

Word Input
Offset

0 to 9998

Specifies the offset address into the internal Modbus
database for network requests for Modbus function 4
commands. For example, if the value is set to 150, an
address request of 0 returns the value at register 150 in the
database.

Output Offset

0 to 9998

Specifies the offset address into the internal Modbus
database for network requests for Modbus function 1, 5 or 15
commands. For example, if the value is set to 100, an
address request of 0 corresponds to register 100 in the
database.

Holding Register
Offset

0 to 9998

Specifies the offset address in the internal Modbus database
for network requests for Modbus function 3, 6, or 16
commands. For example, if the value is set to 50, a request
for address 0 corresponds to the register 50 in the database.