Reference MVI69-FLN

♦ CompactLogix Platform

FA Control Network Communication Module

ProSoft Technology, Inc.

Page 109 of 137

November 3, 2008

Token and frames

As patterns of the frames to be sent with a token, the following 6 types are
available.

1 When there is no cyclic data to be sent: Only a token is transmitted.
2 When there is only cyclic data: a token is transmitted together with cyclic

frame.

3 When there is only cyclic data and this cyclic data is sent in divided form:

Only the cyclic frames are transmitted and a token is attached to the last
cyclic frame.

4 When there is only message data: The message frame is transmitted and

then a token is transmitted.

5 When there are cyclic data and message data: The message frame is

transmitted and then the cyclic frame is transmitted together with a token.

6 When there are cyclic data and message data and the cyclic data is sent in

divided form: The message frame is transmitted and then only the cyclic
frames are transmitted and a token is attached to the last frame.