ProSoft Technology MVI69-PDPMV1 User Manual

Page 126

Advertising
background image

Mailbox Messaging

MVI69-PDPMV1 ♦ CompactLogix or MicroLogix Platform

User Manual

PROFIBUS DPV1 Master

Page 126 of 225

ProSoft Technology, Inc.

July 8, 2011

4.4.16 Mailbox Message: Alarm Indication

This message indicates to the application that a DPV1 slave has transferred an
alarm message to the Master. This mailbox message is sent spontaneously by
the module; the module itself initiates the mailbox communications.

Detailed information about the cause of the alarm is presented in extended words
1 to 3 and in the message data field (see below).

Command and Response Layout: Alarm Indication

Command

Response

Message ID

(ID)

(ID)

Message information

4002h

0002h

Command

0022h

0022h Alarm

Indication

Data size

(request length)

0000h

Frame count

0001h

0001h

Frame number

0001h

0001h

Offset high

0000h

0000h

Offset low

0000h

0000h

Extended word 1

Slave

Address

Slot Number

-

Extended word 2 Seq Number Alarm Spec

Ack

-

Extended word 3 Alarm Type

Ext Diag

-

Extended word 4

-

-

Extended word 5

-

-

Extended word 6

-

-

Extended word 7

-

-

Extended word 8

Fault Information

-

Message Data byte 1

Data 1

Message Data byte 2

Data 2

Message Data byte 3

Data 3

… …

Message Data byte n

Data n


Slave Address
Station address of the slave that issued the alarm.

Slot Number
Used by the slave to indicate the source of the alarm. Range 0 to 254.

Seq Number
Unique identification number of the alarm. Range 0 to 31.