MVI69-PDPMV1 ♦ CompactLogix or MicroLogix Platform

Mailbox Messaging

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 97 of 225

July 8, 2011

Acyclic Message Status Word
Refer to Acyclic Message Status Word (page 128).

Slave Address
Range 1 to 125; specifies the slave from which to read the configuration.

Error Code [1 … 4]
If "Return Code" equals 3080h ("Negative indication from lower layer"), status
values according to the DP-specification may be available in "Error Code 1",
Error Codes 2 through 3 are reserved. Refer to Mailbox Messaging Error Codes
(page 128).

Return Code
Refer to Mailbox Messaging Error Codes (page 128).

Fault Information
If "Invalid other" is returned in the Acyclic Message Status Word in the header of
the response, information about the fault can be found here. Refer to Acyclic
Message Status Word (page 128).

0100h: Address out of range.

0A00h: Failed to execute request. Refer to Return Codes (page 129) for
additional information.

0B00h: Remote station failure. Refer to Return Codes (page 129) for additional
information.

FF00h: Module not initialized.

Identifier Bytes [1 … n]
Refer to EN50170 Vol. 2 for information on the structure of these bytes. In
addition, refer to the documentation provided with the slave device for more
information.