M_me_nb_1, M_me_nc_1 – ProSoft Technology MVI69-101S User Manual

Page 39

Advertising
background image

Configuring the MVI69-101S Module

MVI69-101S ♦ CompactLogix or MicroLogix Platform

IEC 60870-5-101 Slave Communication Module

ProSoft Technology, Inc.

Page 39 of 149

March 16, 2009

This section takes the following parameters:

Point

#

DB

address

Groups
Default

Deadband

IV DB Bit

Each point is one word and the DB address value corresponds to the word offset
in the database.

The Database address value should be located in a database area that is
constantly being moved from the CompactLogix or MicroLogix processor to the
MVI69-101S module. Therefore, this value should be configured in an area that
is used on a Backplane Command Function 1.

Refer to the Group Codes section for a listing of Group Codes.

2.9 [M_ME_NB_1]

This section defines the monitored measured value, scaled database for the
slave device emulated. This information is sourced from the database and is
transferred to the remote master unit. Each point occupies a word position in the
database. The IOa for the parameters for each object are determined by adding
the Point # in the following section to the value of the M_ME_NB parameter
offset parameter set in the previous section.

This section takes the following parameters:

Point

#

DB

address

Groups
Default

Deadband

IV DB Bit

Each point is one word and the DB address value corresponds to the word offset
in the database.

The Database address value should be located in a database area that is
constantly being moved from the CompactLogix or MicroLogix processor to the
MVI69-101S module. Therefore, this value should be configured in an area that
is used on a Backplane Command Function 1.

Refer to the Group Codes section for a listing of Group Codes.

2.10 [M_ME_NC_1]

This section defines the monitored short-float point database for the slave device
emulated. This information is sourced from the database and is transferred to the
remote master unit. Each point occupies 4-byte positions in the database. The
IOa for the parameters for each object are determined by adding the Point # in
the following section to the value of the M_ME_NC Parameter Offset parameter
set in the previous section.