ProSoft Technology MVI71-DNP User Manual

Page 154

Advertising
background image

MVI71-DNP ♦ PLC Platform

Reference

DNP 3.0 Master/Slave Communication Module

Page 154 of 172

ProSoft Technology, Inc.

August 23, 2007

Object

Request

Response

Obj Var Description

Func
Codes

Qual
Codes
(hex)

Func
Codes

Qual
Codes
(hex)

Data
Size
(bits)

Notes

4

16-Bit Analog Input
Without Flag

1

06

129, 130

00, 01

16

Master will
generate and
process this
variation.

31

0

Frozen Analog Input
– All Variations

1

32-Bit Frozen
Analog Input

40

2

16-Bit Frozen
Analog Input

24

3

32-Bit Frozen
Analog Input With
Time To Freeze

88

4

16-Bit Frozen
Analog Input With
Time To Freeze

72

5

32-Bit Frozen
Analog Input
Without Flag

32

6

16-Bit Frozen
Analog Input
Without Flag

16

32 0 Analog

Change

Event – All
Variations

1 06,

07,

08

24

Master will
generate this
variation

1

32-Bit Analog
Change Event
Without Time

1

06, 07,
08

129, 130

17, 28

40

Master will
generate and
process this
variation (16 bit
data).

2

16-Bit Analog
Change Event
Without Time

1

06, 07,
08

129, 130

17, 28

24

Master will
generate and
process this
variation.

3

32-Bit Analog
Change Event With
Time

1

06, 07,
08

129, 130

17, 28

88

Master will
generate and
process this
variation (16 bit
data).

4

16-Bit Analog
Change Event With
Time

1

06, 07,
08

129, 130

17, 28

72

Master will
generate and
process this
variation.

33 0 Frozen

Analog

Event – All
Variations

1

32-Bit Frozen
Analog Event
Without Time

40

Advertising