3 orifice (differential) meter with gas product – ProSoft Technology PTQ-AFC User Manual

Page 232

Advertising
background image

Reference PTQ-AFC

♦ Modicon Quantum Platform

User Manual

Liquid and Gas Flow Computer for Hydrocarbon Products

Page 232 of 259

ProSoft Technology, Inc.

June 23, 2011

Additional areas are also included in the default archive data, according to the
meter type and product group associated with the meter.
The cumulative meter alarms are defined as follows:

Offset

Description

0

Current archive, daily, cumulative meter alarm: Input out of range, temperature

1

Current archive, daily, cumulative meter alarm: Input out of range: pressure

2

Current archive, daily, cumulative meter alarm: Input out of range: differential
pressure

3

Current archive, daily, cumulative meter alarm: Input out of range: flowing density

4

Current archive, daily, cumulative meter alarm: Input out of range: water content

5

Current archive, daily, cumulative meter alarm: Differential Pressure Low

6

Current archive, daily, cumulative meter alarm: Orifice Pressure Exception

7

Current archive, daily, cumulative meter alarm: Accumulation overflow

8

Current archive, daily, cumulative meter alarm: Orifice characterization error

9

Not Used

10

Current archive, daily, cumulative meter alarm: Current archive, daily, cumulative
meter alarm: Analysis characterization error

11

Current archive, daily, cumulative meter alarm: Compressibility calculation error

12

Current archive, daily, cumulative meter alarm: Reference density error

13

Current archive, daily, cumulative meter alarm: Temperature correction error

14

Current archive, daily, cumulative meter alarm: Vapor pressure error

15

Current archive, daily, cumulative meter alarm: Pressure correction error

The cumulative status bits are defined as follows:

Offset

End Offset

00

Stream 1 active

01

Stream 2 active

02

Stream 3 active

03

Stream 4 active

11

Meter enabled

12

Backplane Communication Fault

13

Measurement Configuration Changed

14

Power up

15

Cold Start

The following 20 words (default configuration) will depend on the meter type and
product group as follows:

11.6.3 Orifice (Differential) Meter with Gas Product

Start Offset

End Offset

Data Format

Type

Description

10

11

Accumulator Snapshot

Accumulator totalizer, net

12

13 Floating

point

Snapshot

Accumulator residue, net

14

15

Floating point

Flow weighted average

Flow rate, net

16

17

Floating point

Flow weighted average

Temperature

18

19

Floating point

Flow weighted average

Pressure

20

21

Floating point

Flow weighted average

Differential pressure

22

Word

Flow

weighted

average

Relative density, e-4

23

Word

Flow

weighted

average

Compressibility, reference, e-4

Advertising
This manual is related to the following products: