PLX8x-MNET-61850 ♦ Communication Gateway

ProSoft 61850 Configuration Manager

Modbus TCP/IP to IEC 61850

User Manual

ProSoft Technology, Inc.

Page 47 of 228

May 14, 2014

2.4.2 Schneider Electric PLC Device Configuration

Configuration

After the IEC 61850 Data Attributes to be mapped in the gateway have been
chosen, then double-click, or right-click on the Quantum, Premium, or M340 icon,
and choose C

ONFIGURE

.

This will bring up the MODBUS Mapping Tool window.

On the Modbus Mapping Tool window the Data Attribute is automatically showing
on the left-hand side of the window. The right-hand side of the window is for
mapping IED data to the gateway’s Modbus Client. This is the data the gateway
will push to the Modbus server.

Enable

Options for this Modbus command are
E

NABLE

A

LL

C

OMMANDS

-

C

ONTINUOSLY

E

NABLE

A

LL

C

OMMANDS

- O

N

D

ATA

C

HANGE

D

ISABLED

The default is E

NABLE

A

LL

C

OMMANDS

-

O

N

D

ATA

C

HANGE

.

This means that the data will only be pushed from the ProSoft gateway to the
PLC when the data coming from changes in the gateway's internal database.
This keeps the network traffic at a minimum.