Programmable Signal Inputs

The UPS incorporates four programmable signal inputs: one RS-232
input, two connectivity card inputs, and one REPO terminal input. See
Figure 18 on page 53 for the locations of the ports. Configure the inputs
with the “Signal Inputs” setting in “User Settings” on page 40.

Table 6 shows the programmable settings for the signal inputs. Table 7
shows the operation logic for the signal inputs.

Table 6. Programmable Signal Inputs

Signal

Description

Not Used

The input operates only as a serial input (RxD) or has no function.

Force Bypass

If active, the UPS is forced to static bypass operation regardless of
the bypass status.

Remote Shutdown

If active, the UPS output turns off after a user-defined remote
shutdown delay. The batteries continue charging. Inactive input
does not abort the shutdown countdown and does not cause the
UPS to start up automatically.

Delayed
Shutdown
(and restart)

If active, the UPS output turns off after a user-defined delayed
shutdown delay. The batteries continue charging. Inactive input
does not abort the shutdown countdown but will cause the UPS to
start up automatically if the input voltage exists.

On Generator

If active, synchronization is disabled and the UPS transfers to
bypass.

Building Alarm 1

If active, the UPS generates the “Building Alarm 1” alarm.

Table 7. Polarity Options

Input

Description

High

Active state on high voltage (+Udc) level

Low

Active state on low voltage (GND or -Udc) level