ENVISION CONSOLE INSTALLATION MANUAL

LonWorks Name

SNVT Type

SNVT Index

SCPT Reference

SCPT Index

UCPT Index

Occupied Cooling Setpoint Input (Read/Write)

Standby Cooling Setpoint Input (Read/Write)

Unoccupied Cooling Setpoint Input (Read/Write)

Occupied Heating Setpoint Input (Read/Write)

Standby Heating Setpoint Input (Read/Write)

Unoccupied Heating Setpoint Input (Read/Write)

nciMinClgSetpt

SNVT_temp_p

105

4

Minimum Cooling Setpoint Input (Read/Write)

nciMaxHtgSetpt

SNVT_temp_p

105

3

Maximum Heating Setpoint Input (Read/Write)

nvoSpaceTemp

SNVT_temp_p

105

Space or Zone Temperature Value (Read Only)

nvoDischAirTemp

SNVT_temp_p

105

Discharge Air Temp

Field Supplied Only (Read Only)

nvoEffClgSetpt

SNVT_temp_p

105

Effective Cooling Setpoint Value (Read Only)

nviSpaceTemp

SNVT_temp_p

105

Space or Zone Temperature Value Override(Write)

nvoEffHtgSetpt

SNVT_temp_p

105

Effective Heating Setpoint Value (Read Only)

nciAux5LevP

SNVT_lev_percent

81

Dehumidification Setpoint (Read/Write)

nciAux1Temp

SNVT_temp_p

105

147

Heating Freeze Protection Temperature Setpoint Value (Read/Write)

nciAux2Temp

SNVT_temp_p

105

148

Heating Freeze Protection Temperature Setpoint Value (Read/Write)

1st Stage Compressor Heating Output (Read Only)

1st Stage Compressor Cooling Output (Read Only)

Fan Output (Read Only)

Unit Mode of Operation (Read Only)

Unit Alarm mode (Read Only)

nciPropBand

SNVT_temp_diff_p

147

177

Heating/Cooling Prop Band Input (Read/Write)

nciRemoteSetptMin

SNVT_temp_diff_p

147

98

Warm/Cool Adjust Span (Read/Write)

nciRemoteSetptMax

SNVT_temp_diff_p

147

97

Warm/Cool Adjust Offset Value (Read/Write)

nciTempOffset

SNVT_temp_diff_p

147

11

Space or Zone Temperature Sensor Calibration Input (Read/Write)

nviSetpoint

SNVT_temp_p

105

General Setpoint Input (Read/Write)

nvoHtgFrzPro1Tmp

SNVT_temp_p

105

Heating Freeze Sensing Temperature Value (Read Only)

nvoHtgFrzSetpt

SNVT_temp_p

105

Heating Freeze Sensing Temperature Setpoint Value (Read Only)

nvoAlarms

SNVT_lev_cont

21

Alarms Enumerated [0=no alarms, 1=condensate alarm, 2=Compressor Hi Discharge

Pressure alarm, 3=Compressor low Suction Pressure alarm, 4=Freeze sensing

alarm, 8=Faulty Freeze Sensor alarm,

9=Loss of Charge]

(Read Only)

nvoPWMOut

SNVT_volt

44

ECM PWM Control signal value (Read Only)

nvoECMOvrd

SNVT_volt

44

ECM PWM Control signal Override (Read/Write)

nvoHumidity

SNVT_volt

44

Space Humidity value (Read Only)

nviAO2

SNVT_lev_percent

81

Spare PWM Output AO2 Command (Write)

nvoAO2

SNVT_lev_percent

81

Spare PWM Output AO2 Value (Read Only)

nciBypassTime

SNVT_time_min

123

SCPTbypassTime

34

Temporary Occupancy Time Period Input (Read/Write)

nvoEffectOccup

SNVT_occupancy

109

Effective Occupancy State (Read Only)

nviOccManCmd

SNVT_occupancy

109

Occupancy Override Command Input (Read/Write)

nviEmergOverride

SNVT_hvac_emerg

103

Emergency Override Input (Read/Write)

nvoFanStatus

SNVT_lev_disc

22

Fan Output Status (Read Only)

nvoAccStatus

SNVT_lev_disc

22

Accessory 2 Output Status (Read Only)

nvoLP_WVStatus

SNVT_lev_disc

22

Accessory 1 Output Status (Read Only)

nvoAlarmStatus

SNVT_lev_disc

22

Alarm Output Status (Read Only)

nviAlarmReset

SNVT_lev_disc

22

Alarm Reset Input (Read/Write)

nviFanSpeedCmd.StateSNVT_switch

95

Network equivelant of a thermostatic 'G' call. (Write)

nviComprEnable.State SNVT_switch

95

Network equivelant of a thermostatic 'Y1' call. (Write)

nviComprEnable.State SNVT_switch

95

Network equivelant of a thermostatic 'Y2' call. (Write)

nvoRV1Status

SNVT_lev_disc

22

Reversing Valve Output Status (Read Only)

nviOccSchedule

SNVT_tod_event

128

Occupancy Supervisory Scheduler Command Input (Read/Write)

nvoCompFanProv

SNVT_lev_disc

22

Compressor/Fan Proving Switch Status (Read Only)

nvoDirtyFilter

SNVT_lev_disc

22

Dirty Filter Switch Status (Read Only)

nvoComp2Status

SNVT_lev_disc

22

Compressor Hi Capacity Command Status (Read Only)

nviBO5

SNVT_lev_disc

22

Command for output BO5 used for Emg Heat-Interlocked with Fan DP9Read/Write)

nviBO9

SNVT_lev_disc

22

Command for output BO9(Read/Write)

nvoBO5

SNVT_lev_disc

22

Value output for BO5 used for Emg Heat (Read Only)

nvoBO9

SNVT_lev_disc

22

Value output for BO9 (Read Only)

nviDehumEna.State

SNVT_lev_disc

22

Dehumidification command-like a Humidistat (Read/Write)

Point Description

60

LonWorks

SCPTsetPnts

nciSetpoints

SNVT_temp_setpt

106

nvoUnitStatus

SNVT_hvac_type

112

LonWorks

Envision Console Controls