Envision console controls, Bacnet, Envision console installation manual – Envision Peripherals Water-Furnace IM1609 10 User Manual

Page 38

Advertising
background image

37

ENVISION CONSOLE INSTALLATION MANUAL

Object Type

Type Enumeration

Instance

Name

Enumeration

Analog Value

2

1

Present_Value

85

WFI##########.Occupied Cool.Present_Value

Occupied Cooling Setpoint Input (Read/Write)

Standby Cooling Setpoint Input (Read/Write)

Analog Value

2

2

Present_Value

85

WFI##########.Unoccupied Cool.Present_Value

Unoccupied Cooling Setpoint Input (Read/Write)

Analog Value

2

3

Present_Value

85

WFI##########.Occupied Heat.Present_Value

Occupied Heating Setpoint Input (Read/Write)

Standby Heating Setpoint Input (Read/Write)

Analog Value

2

4

Present_Value

85

WFI##########.Unoccupied Heat.Present_Value

Unoccupied Heating Setpoint Input (Read/Write)

Minimum Cooling Setpoint Input (Read/Write)

Maximum Heating Setpoint Input (Read/Write)

Analog Input

0

1

Present_Value

85

WFI##########.Space Temp.Present_Value

Space or Zone Temperature Value (Read Only)

Analog Input

0

2

Present_Value

85

WFI##########.Discharge Air Temp.Present_Value

Discharge Air Temp

Field Supplied Only (Read Only)

Analog Input

0

3

Present_Value

85

WFI##########.Effective Clg Setpt.Present_Value

Effective Cooling Setpoint Value (Read Only)

Analog Output

1

4

Present_Value

85

WFI##########.Space temp Ovrd.Present_Value

Space or Zone Temperature Value Override(Write)

Analog Input

0

4

Present_Value

85

WFI##########.Effective Htg Setpt.Present_Value

Effective Heating Setpoint Value (Read Only)

Analog Value

2

9

Present_Value

85

WFI##########.Dehumidify Setpt.Present_Value

Dehumidification Setpoint (Read/Write)

Analog Value

2

10

Present_Value

85

WFI##########.Low Temp Limit Adj.Present_Value

Heating Freeze Protection Temperature Setpoint Value (Read/Write)

Heating Freeze Protection Temperature Setpoint Value (Read/Write)

1st Stage Compressor Heating Output (Read Only)

1st Stage Compressor Cooling Output (Read Only)

Fan Output (Read Only)

Multistate Input

13

2

Present_Value

85

WFI##########.Mode.Present_Value

Unit Mode of Operation (Read Only)

Unit Alarm mode (Read Only)

Heating/Cooling Prop Band Input (Read/Write)

Analog Value

2

6

Present_Value

85

WFI##########.Remote Setpt Span.Present_Value

Warm/Cool Adjust Span (Read/Write)

Analog Value

2

7

Present_Value

85

WFI##########.Remote Setpt Bias.Present_Value

Warm/Cool Adjust Offset Value (Read/Write)

Analog Value

2

8

Present_Value

85

WFI##########.Space Temp Offset.Present_Value

Space or Zone Temperature Sensor Calibration Input (Read/Write)

Analog Output

1

1

Present_Value

85

WFI##########.Space Setpoint.Present_Value

General Setpoint Input (Read/Write)

Analog Input

0

6

Present_Value

85

WFI##########.Water Coil Temp.Present_Value

Heating Freeze Sensing Temperature Value (Read Only)

Analog Input

0

7

Present_Value

85

WFI##########.Low Temp Limit.Present_Value

Heating Freeze Sensing Temperature Setpoint Value (Read Only)

Analog Input

0

9

Present_Value

85

WFI##########.Alarms Enumerated.Present_Value

Alarms Enumerated [0=no alarms, 1=condensate alarm, 2=Compressor Hi Discharge

Pressure alarm, 3=Compressor low Suction Pressure alarm, 4=Freeze sensing

alarm, 8=Faulty Freeze Sensor alarm,

9=Loss of Charge]

(Read Only)

Analog Input

0

8

Present_Value

85

WFI##########.ECM Cmd Output.Present_Value

ECM PWM Control signal value (Read Only)

Analog Output

1

2

Present_Value

85

WFI##########.ECM Fan Ovrd.Present_Value

ECM PWM Control signal Override (Read/Write)

Analog Input

0

5

Present_Value

85

WFI##########.Space Humidity.Present_Value

Space Humidity value (Read Only)

Analog Output

1

3

Present_Value

85

WFI##########.AO2 Override.Present_Value

Spare PWM Output AO2 Command (Write)

Analog Input

0

10

Present_Value

85

WFI##########.AO2 Value.Present_Value

Spare PWM Output AO2 Value (Read Only)

Analog Value

2

5

Present_Value

85

WFI##########.Temporary Occ Time.Present_Value

Temporary Occupancy Time Period Input (Read/Write)

Multistate Input

13

1

Present_Value

85

WFI##########.Effective Occupancy.Present_Value

Effective Occupancy State (Read Only)

Multistate Output

14

1

Present_Value

85

WFI##########.Occupancy Command.Present_Value

Occupancy Override Command Input (Read/Write)

Multistate Output

14

6

Present_Value

85

WFI##########.Emergency Override.Present_Value

Emergency Override Input (Read/Write)

Binary Input

3

1

Present_Value

85

WFI##########.Fan Cmd Status.Present_Value

Fan Output Status (Read Only)

Binary Input

3

6

Present_Value

85

WFI##########.Accessory 2 Output.Present_Value

Accessory 2 Output Status (Read Only)

Binary Input

3

5

Present_Value

85

WFI##########.Accessory 1 Output.Present_Value

Accessory 1 Output Status (Read Only)

Binary Input

3

8

Present_Value

85

WFI##########.Alarm Status.Present_Value

Alarm Output Status (Read Only)

Multistate Output

14

7

Present_Value

85

WFI##########.Alarm Reset.Present_Value

Alarm Reset Input (Read/Write)

Multistate Output

14

2

Present_Value

85

WFI##########.Fan Command (G).Present_Value

Network equivelant of a thermostatic 'G' call. (Write)

Multistate Output

14

3

Present_Value

85

WFI##########.Compressor Cmd (Y1).Present_Value

Network equivelant of a thermostatic 'Y1' call. (Write)

Multistate Output

14

3

Present_Value

85

WFI##########.Compressor Cmd (Y2).Present_Value

Network equivelant of a thermostatic 'Y2' call. (Write)

Binary Input

3

4

Present_Value

85

WFI##########.Reversing Valve.Present_Value

Reversing Valve Output Status (Read Only)

Occupancy Supervisory Scheduler Command Input (Read/Write)

Compressor/Fan Proving Switch Status (Read Only)

Binary Input

3

7

Present_Value

85

WFI##########.Dirty Filter (BI-12).Present_Value

Dirty Filter Switch Status (Read Only)

Binary Input

3

3

Present_Value

85

WFI##########.Comp Hi Capacity Cmd.Present_Value

Compressor Hi Capacity Command Status (Read Only)

Multistate Output

14

8

Present_Value

85

WFI##########.Emergency Heat BO5.Present_Value

Command for output BO5 used for Emg Heat-Interlocked with Fan DP9Read/Write)

Multistate Output

14

9

Present_Value

85

WFI##########.BO9.Present_Value

Command for output BO9(Read/Write)

Binary Input

3

9

Present_Value

85

WFI##########.BO5 Output.Present_Value

Value output for BO5 used for Emg Heat (Read Only)

Binary Input

3

10

Present_Value

85

WFI##########.BO9 Output.Present_Value

Value output for BO9 (Read Only)

Multistate Output

14

10

Present_Value

85

WFI##########.Dehum Cmd.Present_Value

Dehumidification command-like a Humidistat (Read/Write)

Point Description

Object Identifier

Property

BACnet

Full Reference

BACNet

Envision Console Controls