Installation – Empire Products FAW-55IP User Manual

Page 8

Advertising
background image

12429-10-0408

Page 8

Figure 6

Electrode and pilot must be kept clean. Clean through pilot access

hole with a small brush (toothbrush) and water.
Proper Main Burner Flame

The correct flame will be a short blue inner flame with a much

larger light blue outer flame. The main burner (Figure 7) shows the

approximate height of each part of the flame for each gas. The burner

does not have a primary air adjustment. The flame will be correct if

the factory-set pressure and orifice opening are used. After the furnace

has been operating, the burner ports may be blocked by foreign matter

carried in by combustion air. Therefore, cleaning of the burner may

be needed for proper flame.
To clean burner port disconnect the gas supply to the valve, and remove

the eight screws fastening the burner door. After removing the burner

door from the combustion chamber, remove rear burner, pilot burner

and front burner. With front and rear burners removed from furnace,

force water into the ribbon ports and dry with air pressure.

Figure 7

Replacing Fan and Oiling the Motor

The fan motor should be cleaned and oiled once each heating season.

To reach the motor, withdraw the metal shroud surrounding the fan

blade by removing the screws on each side. Oil holes are located on

the top at each end of the motor. Use a few drops of #10 motor oil.

To clean the motor, blow air through its ventilation openings with a

vacuum cleaner or low pressure air source.
If fan motor is replaced, the silicone rubber gaskets, see page 14, Index

No. 5, Part No. 712059 should also be replaced. The gaskets must be

stretched to fit the motor bolts into the gasket holes and then the motor

and gaskets installed on the motor mounting bars.

Checking Manifold Pressure

Both Propane and Natural gas valves have a built-in pressure regulator

in the gas valve. Natural gas models will have a manifold pressure

of approximately 3.5” w.c. (.871kPa) at the valve outlet with the inlet

pressure to the valve from a minimum of 5.0” w.c. (1.24kPa) for the

purpose of input adjustment to a maximum of 10.5” w.c. (2.615kPa)

Propane gas models will have a manifold pressure approximately 10.0”

w.c. (2.49kPa) at the valve outlet with the inlet pressure to the valve

from a minimum of 11.0” w.c. (2.739kPa) for the purpose of input

adjustment to a maximum of 13.0” w.c. (3.237kPa).
A 1/8” (3mm) N.P.T. plugged tapping, accessible for test gauge

connection, is located on the outlet side of the gas control.
The built-in regulator comes on at approximately 1/4th pressure and

full on in 10 seconds.

Figure 5

High Altitudes

For altitudes/elevations above 2,000 feet (610m), input ratings should

be reduced at the rate of 4 percent for each 1,000 feet (305m) above

sea level. Canadian High Altitudes for locations having an elevation

above mean sea level between 2,000 feet (610m) and 4,500 feet (1370m),

the manifold pressure is to be decreased from 3.5” w.c. (.871kPa) to

2.8” w.c. (.697kPa) for Natural Gas and from 10.0” w.c. (2.49kPa) to

8.0” w.c. (1.992kPa) for Propane Gas.
Proper Pilot Flame

The pilot flame (Figure 6) going to the spark must be large enough to

completely cover the sparking area. With the proper flame, only 2 or

3 sparks will occur. More sparks indicate a small pilot flame and no

ignition with spark stopping after approximately 90 seconds generally

means not enough flame.
To adjust pilot flame remove the pilot cover screw on the control valve

(Figure 5), and turn the adjustment screw clockwise to reduce flame.

Replace pilot cover screw to eliminate gas leakage.
The pilot flame will appear large. A blue nearly horizontal flame is

proper. The spark gap must be 1/8” (3mm) . A larger gap can result

in the spark occurring some other place. The pilot flame and the spark

gap are factory checked and tested.
After use, cleaning may be required for the proper flame.
Safety Lockout

S8600H module provides 100 percent shutoff, or safety lockout.

If the pilot fails to light within 90 seconds, the control system

will shut down. The control system must be reset by setting

the thermostat below room temperature for one minute or by

turning off power to the module for one minute.

4” (102mm) NAT
6” (152mm) LP

1 ½”(38mm) NAT
1/4” (6mm) LP