VU443A; VU444A; VU843A; VU844A FAN COIL VALVE ACTUATORS

95C-10883—03

2

Fig. 1. Mounting Dimensions in inches (mm).

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow them

could damage the product or cause a hazardous condi-

tion.

2. Check the ratings given in the instructions and on the

product to make sure the product is suitable for your

application.

3. Installer must be a trained, experienced service techni-

cian.

4. After installation is complete, check out product opera-

tion as provided in these instructions.

CAUTION

1.

Disconnect power supply before connecting wir-

ing to prevent electrical shock of equipment dam-

age.

2.

On 24V systems, never jumper the valve coil ter-

minals even temporarily. This can burn out the

heat anticipator in the thermostat.

To Install and Remove Actuator

INSTALLING ACTUATOR ON VU-SERIES VALVE BODY
ASSEMBLY

1. Orient slot in shaft of VU-series valve body toward

notch in side of body (i.e. 90° to water flow.) See

Fig.2. This lifts the ball off seat, prevents damage to the

ball seal while soldering, and makes actuator attach-

ment easier.

2. Install valve body into pipe.

3. Wiring connections may be made either before or after

the actuator is installed on the valve body.

4. Place manual operating lever on the actuator in the

MAN. OPEN position.

5. Line up motor coupling to slot in shaft of body and fit the

head onto the valve body, ensuring that the shaft seats

correctly. (See Fig. 2).

6. Snap actuator onto body by pressing down.

7. Make wiring connections. Refer to wiring section for

proper instructions.

Inspect the actuator installation and the valve body to ensure

that all connections and adjustments have been correctly

made. Adjust the thermostat or controller connected to the

valve so that the valve runs through its cycle. Make sure the

valve runs smoothly and positively from closed to open to

closed again.

VU52 OR VU53 VALVE WITH ACTUATOR

2-3/8

(60)

7/8 DIA. (22)

1-1/2

(38)

3-3/4

(133)

15/32 (12)

M32204

2

1

HEIGHT NEEDED TO REMOVE ACTUATOR OR COVER.

OPENING FOR 1/2 IN. CONDUIT ON OPPOSITE SITE OF

MANUAL LEVER FOR ALL MODELS.

1

2

VU53 AND VU54 VALVE DIMENSIONS WITH ACTUATOR

VU ACTUATOR

3/8

(10)

1-3/4

(44)

1-3/4

(44)

A

A

B

AB

3/8

(10)

A

1-3/4

(44)

1-3/4

(44)

B

3-WAY

7/8 (23)

2-WAY

VALVE BODY SIZE

1/2 IN. SWEAT
3/4 IN. SWEAT

1 IN. SWEAT

M32203

A

1-5/6 (33)
1-3/8 (35)

1-11/16 (43)

B

1-5/6 (33)

1-11/16 (43)
1-11/16 (43)