Wiring, Operation, Caution – Honeywell VU443A User Manual

Page 3

Advertising
background image

VU443A; VU444A; VU843A; VU844A FAN COIL VALVE ACTUATORS

3

95C-10883—03

Fig. 2. Installing new actuator.

REMOVING ACTUATOR FROM THE VU-SERIES VALVE
BODY ASSEMBLY (SEE FIG. 3)

NOTE: It is not necessary to drain the system if the valve

body assembly remains in the pipeline.

1. Switch power supplies OFF. Disconnect electrical leads,

carefully noting the position and colour of each lead.

2. Place the manual operating lever in the MAN. OPEN

position.

3. Remove actuator by depressing locking button and lift-

ing straight up.

Fig. 3. Removing actuator from valve body.

WIRING

Disconnect the power supply before connecting wiring to

prevent electrical shock or equipment damage. All wiring must

comply with local codes and ordinances.

TO ATTACH FLEXIBLE CONDUIT

1. Strip cable jacket.

2. Fit conduit strain relief onto cable.

3. Slide strain relief nut over wires.

4. Connect cable and actuator wires.

5. Slide cable wires down through slot in the wiring hole,

so that the strain relief nut is inside the actuator hous-

ing.

6. Secure nut onto strain relief.

7. Install actuator cover.

Fig. 4. Typical wiring for VU40-series actuator.

Fig. 5. T822 Thermostat, VU80-series actuator hookup.

OPERATION

CAUTION

On 24V systems, never jumper the valve coil

terminals even temporarily. This can burn out the

heat anticipator in the thermostat.

AUTOMATIC OPERATION
On a call for heat or cool by the fan coil thermostat, the valve

motor operates, opening the valve. When the call ends, the

valve closes by integral spring return.

ENSURE SHAFT

SLOT POINTS

TOWARDS NOTCH

ON SIDE OF BODY

FOR FITTING INTO

ENGAGING SHAFT

ACTUATOR

COUPLING

M32206

NOTCH

2. DEPRESS

LOCKING

BUTTON

3. LIFT ACTUATOR

STRAIGHT

UP

1. PLACE MANUAL

LEVER IN OPEN

POSITION

AUTO

M32207

OPEN

ELECTRONICS

L1

(HOT)

L2

FAN COIL THERMOSTAT

(TYPICALY T4039, T6380, TB6570)

MOTOR

VU ACTUATOR

L1

L2

H/C

M32082B

L1

(HOT)

L2

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND

OVERLOAD PROTECTION AS REQUIRED.
CONNECT BLACK LEADWIRE TO THERMOSTAT.

T822

T822

T822

VU VALVE

VU VALVE

VU VALVE

M32083

1

2

1

2

2

2