MANUAL OPERATION
The 2-way normally closed and 3-way motorized valve

actuators can be opened manually by lifting the manual

opening lever over the stop and pushing slowly and firmly to

the MAN. OPEN position. The stop permits the valve to be

locked in the open position. The valve returns to automatic

position when it is energized.

NORMALLY CLOSED
With the manual opener set to AUTO and the actuator

energized, the A port is opened as shown in Fig. 6A and 7A.

When the actuator is de-energized, a spring-return

mechanism drives the valve to the port A closed position as

shown in Fig. 6B and 7B. The valve can also be opened with

no electrical power by moving the manual opening lever over

the stop and pushing slowly and firmly to the MAN. OPEN

position. The stop permits the valve to be locked in an open

position. The valve returns to the automatic position when the

valve is energized.

NORMALLY OPEN
With the manual opener set to AUTO and the actuator

energized, the A port is closed as shown in Fig. 6B.

NOTE: Inlet and Outlet Ports are indicated by a flow direc-

tion arrow on the valve body.

Fig. 6. Actuator operation for normally closed 2-way

valve.

Fig. 7. Actuator operation for normally closed 3-way

valve.

CHECKOUT

SET TO HEATING MODE

1. Raise the setpoint on the zone thermostat above the

room temperature to initiate a call for heat.

2. Observe all control devices - the valve should open.

3. Lower the setpoint on the zone thermostat below the

room temperature.

4. Observe the control devices. The valve should close

and the auxiliary equipment should stop.

SET TO COOLING MODE

1. Lower the setpoint on the zone thermostat below the

room temperature to initiate a call for cooling.

2. Observe all control devices - the valve should open.

3. Raise the setpoint on the zone thermostat above the

room temperature.

4. Observe the control devices. The valve should close.

SERVICE

This valve should be serviced by a trained, experienced

service technician.

1. If the valve is leaking, drain the system and check to

see if the O-ring needs replacing.

2. If the gear train is damaged, replace the entire actuator.

See the Installation section. If the motor is burned out,

replace the motor.

3. Wear safety glasses to protect eyes from injury

when removing or installing the large spring clip

that holds the actuator plate to the valve body. Use

proper snap ring pliers to remove or install spring

clip.

NOTE: Honeywell fan coil valves are designed and tested

for silent operation in properly designed and installed

systems; however, water noises can occur as a

result of excessive water velocity or piping noises

can occur in high temperature (higher than 212° F

[100° C]) systems with insufficient water pressure.

Valves are designed for normal cycling operations.

Product life will be shortened if energized continu-

ously or if operated above rated temperatures.

Use VU443/843 actuators ONLY with VU53 2-way normally

close valve bodies. Water hammer may result and actuator

life will be shortened if used on VU54 3-way body.

Use VU444/844 actuators on either VU52 2-way normally

open bodies or VU54 3-way diverting valve bodies. Close-off

pressure ratings will be reduced when used with VU53.

OUT

OPEN POSITION

(POWERED)

IN

OUT

IN

M32202

CLOSED POSITION

(UNPOWERED)

Fig. 6a.

Fig. 6b.

B

FLOW-THROUGH SERVICE PORT

(POWERED)

A

IN

B

OUT

A

M32205

AB

IN

FLOW-THROUGH BYPASS PORT

(UNPOWERED)

AB

IN

Fig. 7a.

Fig. 7b.