C7400S ENTHALPY SYLK BUS SENSOR

62-0332—03

2

BEFORE INSTALLATION

Review the “Specifications” on page 1 before installing the

sensor.

When Installing This Product

1. Read these instructions carefully. Failure to follow them

could damage the product or cause a hazardous

condition.

2. Check ratings given in instructions and on the product to

ensure the product is suitable for your application.

3. Installer must be a trained, experienced service

technician.

INSTALLATION AND SETUP

The following installation procedures should be performed in

the order listed:

1. Mounting — see “Mounting” on this page.
2. Wiring — see “Wiring” on page 3.
3. Checkout — see “Checkout” on page 3.

MOUNTING

IMPORTANT

Avoid mounting in areas where acid fumes or other
deteriorating vapors can attack the metal parts of the
sensor, or in areas where escaping gas or other
explosive vapors are present.

IMPORTANT

The sensor must be mounted in a position that
allows clearance for wiring, servicing, and removal.

The sensor is mounted directly to the sheet metal using self

tapping sheet metal screws or in the air stream using the duct

mounting kit. Use #6 or #8 screws (screws are not provided

and must be obtained separately). Use the dimensions in

Fig. 1 on page 1 as a guide.

The sensor must be mounted to allow air flow through the

sensor housing vent slots on the end or side.

The Sylk Bus sensor communicates with a controller (such as

the JADE™ Economizer Model W7220) on the two-wire

communication bus and can either be wired using a two pin

header or using a side connector. The unit pack Sylk Bus

sensor includes a two pin Euro connector with the packaging.

The SKU number of the Sylk Bus sensor is C7400S. All OAT

(Outdoor Air Temperature), RAT (Return Air Temperature) and

DAT (Discharge Air Temperature) sensors are the same SKU

number. The sensor is set for the appropriate type of sensing

using the three position DIP switch located on the sensor.

OAT position is OFF, OFF, OFF; RAT is ON, OFF, OFF and

DAT is OFF, ON, OFF. During installation the sensors are set

for the the appropriate usage. See “Sylk Bus Sensor Wiring”

on page 3 for DIP switch details.

Once installed, a sensor can be changed to a different

application by simply changing the DIP switch setting.

Sensor Mounting

The sensor can be mounted directly on to the sheet metal of

the unit or can be mounted in the air stream using the duct

mounting kit.

The duct mounting kit contains a rod to hold the sensor in the

duct, a flange to secure the sensor rod to the duct wall and to

fill the hole, and a gasket to prevent air from leaking through

the duct wall. See Fig. 2.

The rod has slots for threading the wire to prevent loose or

hanging wire in the duct and can be adjusted for 6 or 12 inch

length. The flange has extended relief for ease of mounting.

See Fig. 3.

Fig. 2. Duct Mounting Kit (Part # 50053060-001).

Fig. 3. Duct Mounting Adjustments.

ROD - 1 PIECE

FLANGE - 1 PIECE

GASKET - 1 PIECE

M32281

WIRE HOLDER

EXTENDED RELIEF

(FOR CORRECT MOUNTING)

M32282

LENGTH ADJUSTS

TO 6 OR 12 INCHES