C7400S ENTHALPY SYLK BUS SENSOR

3

62-0332—03

WIRING

All wiring must comply with applicable electrical codes and

ordinances, or as specified on installation wiring diagrams.

WARNING

Electrical Shock Hazard.

Can cause severe injury, death or property

damage.

Disconnect power supply before beginning wiring, or

making wiring connections, to prevent electrical shock

or equipment damage.

CAUTION

Equipment Damage Hazard.

Electrostatic discharge can short equipment

circuitry.

Ensure that you are properly grounded before

handling the sensor.

Prepare wiring as follows:

1. Strip 1/2 in. (13 mm) insulation from the conductor.

2. Cut a single wire to 3/16 in. (5 mm). Insert the wire in

the required terminal location and tighten the screw.

3. Pull on each wire in all terminals to check for good

mechanical connection.

Sylk Bus Sensor Wiring

Use Fig. 4 and Table 1 to locate the wiring terminals for each

Sylk Bus sensor.

Use Fig. 4 and Table 2 to set the DIP switches for the desired

use of the sensor.

Fig. 4. Sylk Bus sensor DIP switches.

CHECKOUT

Refer to the JADE™ Economizer Module (Model W7220)

Installation Instructions (Honeywell form 62-0331).

TROUBLESHOOTING

Refer to the JADE™ Economizer Module (Model W7220)

Installation Instructions (Honeywell form 62-0331).

DIP

SWITCH

LABEL

M32271

SYLK BUS

TERMINALS

(1 AND 2)

DIP

SWITCHES

(3)

SYLK BUS

2 PIN “EURO”

CONNECTOR

Table 1. SYLK Bus Sensor Wiring Terminations

a

.

a

Terminals are polarity insensitive.

Terminal

Type

Description

Nbr

Label

1

S-BUS SYLK Bus Sylk Bus Communications

(Sensor Bus)

2

S-BUS SYLK Bus Sylk Bus Communications

(Sensor Bus)

Table 2. SYLK Bus Sensor DIP Switch Settings.

Use

DIP Switch Positions for Switches 1, 2, & 3

1

2

3

DA

a

a

DA = Discharge Air

OFF

ON

OFF

RA

b

b

RA = Return Air

ON

OFF

OFF

OA

c

c

OA = Outside Air

OFF

OFF

OFF