15

System type

Heating cycle rate
(CPH: cycles/hour)

Compressor
cycle rate (CPH)

Adaptive Intelligent
Recovery

Temperature
display

Compressor
protection

0 Gas, oil or electric heat with air conditioning
1

Heat pump (5 minute compressor off time in heating and cooling)

5 For gas or oil furnaces of less than 90% efficiency
1

For steam or gravity systems

3

For hot water systems & furnaces of over 90% efficiency

9

For electric furnaces
[Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]

3 Recommended for most compressors

[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]

1 On

**See page 10

0

Off

0 Fahrenheit
1

Celsius

5 Five-minute compressor off time

**See page 10

[Other options: 0, 1, 2, 3 or 4-minute off time]

Setup Function

Settings & Options

To begin, press and hold the and
buttons until the display changes

Function
number

Press

to change settings

Press

to advance to next function

Press and hold

to exit and save settings

Setting

Installer setup

Follow the procedure below to configure the thermostat to match the installed
heating/cooling system, and customize feature operation as desired.

Setup

Installer system test

After completing the installer setup above, press the

button again to begin a

system test (see next page).

Press and hold both buttons