Wiring, Terminal designations – Honeywell PRO TH4110D User Manual

Page 6

Advertising
background image

Installation Guide

4

Wiring

1

Loosen screw terminals, insert
wires into terminal block, then re-
tighten screws.

2

Push excess wire back into the
wall opening. Keep wires in shaded
area as shown at left.

3

Plug the wall opening with non-
flammable insulation to prevent
drafts from affecting thermostat
operation.

Terminal Designations

W

W Heat relay.

Y

Y Compressor contactor.

G

G Fan relay.

O

O Heat pump changeover valve ener-

gized in cooling.

R

Rc

c Cooling power. Connect to

secondary side of cooling
system transformer.

R

R Heating power. Connect to

secondary side of heating
system transformer.

B

B

Heat pump changeover valve ener-
gized in heating.

C

C Common wire from secondary side

of cooling system transformer.

Terminal
block

NOTES

R & Rc terminals
In single-transformer system, leave metal
jumper in place between R & Rc. Remove
metal jumper if two-transformer system.

Heat pump systems
If wiring to a heat pump, use a small piece of
wire (not supplied) to connect terminals W
and Y.

C terminal
The C (common wire) terminal is optional
when thermostat is powered by batteries.

Wire specifications
Use 18- to 22-gauge thermostat wire.
Shielded cable is not required.

Keep wires in this
shaded area

CAUTION: ELECTRICAL HAZARD. Can cause electrical shock or equipment damage.
Disconnect power before wiring.

Wiring