Table 2. L7224 Controller Operating Sequence

Troubleshooting

When attempting to diagnose system performance, reference the

LED display to help identify specific areas not working properly.

The LED display will scroll “err”, followed by a digit (1-8). See

Table 1 for a description of the error and suggested actions. See

below for a troubleshooting guide.

Action

System Response

Thermostat

calls for heat.

Circulator starts when water temperature is

above Low Limit setting (if applicable). Boiler

temperature is checked. Burner starts when

water temperature is below High Limit setting.

Boiler exceeds

the High Limit.

Burner is turned off. Burner restarts when the

water temperature drops below the High Limit

setting minus the differential.

Thermostat is

satisfied.

Circulator and burner turn off.

Error conditions

1-5.

If an error condition is detected, all outputs

except ZC are shut down. Burner is off. Control

continues to function and restarts when error is

corrected. During the error check sequence, the

system checks for drift in the sensor and

corrosion in the connections.

Error conditions

6-7.

If error condition 6 or 7 occurs, the control has

reset the High Limit, Low Limit and Differential

Setting to a default setting and will continue to

run at those settings. Performance of the system

will be degraded.

Error condition

8.

If the error condition is detected, all outputs

except ZC are shut down. Burner is off. Control

continues to function and restarts when all three

user keys have been pressed longer than 60

seconds.

Table 3. Troubleshooting Guide

a

.

System

Condition

Diagnostic

Condition

Check

Action

Boiler is

cold,

house is

cold

Display is OFF 120 Vac system

power.

Turn system power on.

Display is ON;

TT-LED is OFF

24 Vac T-T

No 24V; replace

control

Display is ON;

TT-LED is OFF

24V present;

disconnect

thermostat,

short T-T

Boiler starts, check

wiring and thermostat

a

. Refer to Fig. 5 for Display and LED locations.

b

. ZC LED ON indicates ZC terminal power is OFF.

c

. ZC LED OFF indicates ZC terminal power is ON.